Falcon user guide – RLE FMS8 User Manual
Page 58
Falcon User Guide
58
Per channel, select the appropriate number to modify
inputs and either pick an item from a menu or type
the value or description for the item selected. If an
option card is present, the system will automatically
recognize the number of points to configure.
Analog Points
Gain for 4-20mA Transducer
(Sensor High Range – Sensor Low Range)/4
Offset for 4-20mA Transducer
Sensor Low Range – Gain
Digital Points
The table represents control values for the output
relays (K1 and K2) and optional relays (K3, K4, K5
and K6). Select the appropriate value of the relay
to activate it, or add the respective values of the
appropriate alarm condition to activate more than
one output relay. Each input can have individual
control values.
Examples:
Relay Control: 2 - Activates relay K2 for either an
analog 2nd Stage High Alarm or a dry contact
change-of-state.
Relay Control: 64 - Activates relay K3 for an analog
2nd Stage Low Alarm.
Relay Control: 35 - Activates relays K1, K2, and K4
for either an analog 2nd Stage High Alarm or
a dry contact change-of-state (1+2+32).
Relay Control: 10 - Activates relay K2 for either
an analog 2nd Stage High or 2nd Stage Low
Alarm (8+2).
K1 Digital Alarm 1
Relay Alarm Condition Value
K1 High2 Analog Alarm 1
K1 Low2 Analog Alarm 4
K2 High2 Analog Alarm 2
K2 Low2 Analog Alarm 8
K2 Digital Alarm 2
K3 High2 Analog Alarm 16
K3 Low2 Analog Alarm 64
K3 Digital Alarm 16
K4 High2 Analog Alarm 32
K4 Low2 Analog Alarm 128
K4 Digital Alarm 32
K5 High2 Analog Alarm 256
K5 Low2 Analog Alarm 1024
K5 Digital Alarm 256
K6 High2 Analog Alarm 512
K6 Low2 Analog Alarm 2048
K6 Digital Alarm 512
Press Enter (
↵) to advance to next channel
or ESC to abort and back up one menu
level.
** System Menu/Help **
SS - System Status
CA - Current Alarms
KA - Kill All Alarms
LM - Log Menu
TI - Display Date/Time
AD - ADC Input Values
MS - Modem Stats
NS - Network Stats
AT - Arp Table
SC - System Confi g
DU - Dump Network Packets
NT - Network Trace
PING - Ping an IP Address
EX - Exit to Bootloader
Enter Menu Selection >
Enter Menu Selection > SC ******
** Main Confi guration Menu **
1. System Menu
2. IP Confi g Menu
3. Modem Confi g menu
4. EIA-485 Confi g menu
5. Factory Menu
6. Load/Save Confi g Data
7. Confi guration Password
8. E-Mail, SMTP Confi g Menu
X. Exit
Enter Menu Selection >
Enter Menu Selection >1
System Confi guration Menu
1. System Name: Falcon Monitoring System
2. Clock: 10/27/00 16:37:17
3. Keypad Access
4. Inputs
5. Relays
6. Battery
7. Analog Averaging: 0
8. Persistent Traps: 0
9. Slave Inputs
10. Slave Relays
11. Schedules
12. BACnet
13. Exit & Save
Enter Menu Selection >
Enter Menu Selection >4
Master Unit: RLE CR Wall Unit
Input Confi guration Menu
Channel #A1 of 32
Current Readings: Raw = 11.652 mA
Calc = 46
1. Type: 4-20
2. Gain: 35
3. Offset: -55
4. High Limit 2: 85
5. High Limit 1: 80
6. Low Limit 1: 60
7. Low Limit 2: 50
8. Relay Cntrl: 0
9. Unit of Measure: ºF
10. Label: Room Temperature
11. Alarm Delay: 0 (Secs)
12. Hysteresis: 0
13. Alarm Dial Out: 1,0,0,0,0
14. BACnet Instance: 0
15. BACnet Units: 0
18. Email Recipients:
19. Alarm Disable Sch: None
20. Previous Channel
21. Next Channel
22. Return
Enter Menu Selection >
Enter Menu Selection >1
Modify Input Type
1. Not Installed
2. Analog 4-20
3. Digital NO
4. Digital NC
5. Digital Status
Enter new type >