Technical data

Series

RXD 260

RXD 350

RXD 520

RXD 680

RXD 1200

Operating mode

Ceiling cassette for combined cooling/heating

Nominal cooling output

1)

kW

2,69

3,59

5,27

6,84

12,48

Nominal heating output

2)

kW

2,96

4,24

6,31

7,72

13,23

Energy efficiency class, cooling

1)

A

A

B

B

C

Energy efficiency ratio EER

1)

3,24

3,21

3,08

3,03

2,81

Energy efficiency class, heating

2)

A

A

C

C

D

Coefficient of performance COP

2)

3,65

3,62

3,25

3,22

3,01

Operating range (room volume), approx.

80

110

160

230

400

Adjustment range, room temperature

°C

+16 to +30

Working range of indoor unit

°C

+15 to +35

Refrigerant

R 410A

Operating pressure max. / per cooling circuit

kPa

4200 / 4200

Air flow rate per stage

m³/h

252/300/360

348/420/510

468/564/624

690/840/1020 978/1188/1380

Noise output per stage

3)

dB(A)

29/37/38

30/37/39

35/41/43

32/39/40

40/47/49

Voltage supply

V/Hz

230 / 1~ / 50

Protection degree

IP

X0

Nom. electrical power consumption, cooling

1)

kW

0,04

0,04

0,05

0,07

0,09

Nom. electrical power consumption, heating

2)

kW

0,04

0,04

0,05

0,07

0,09

Electr. nominal power consumption cooling

1)

A

0,32

0,35

0,42

0,55

0,75

Electr. nominal power consumption heating

2)

A

0,32

0,35

0,42

0,55

0,75

Refrigerant connection, injection pipe

Inches

(mm)

1/4 (6,35)

1/4 (6,35)

1/4 (6,35)

3/8 (9,52)

3/8 (9,52)

Refrigerant connection, suction pipe

Inches

(mm)

3/8 (9,52)

1/2 (12,70)

1/2 (12,70)

5/8 (15,90)

3/4 (19,10)

Condensation connection

mm

19

Condensation pump, delivery height

mm

1000

Dimensions of unit Height

mm

258

258

298

298

298

Width

mm

580

580

580

1110

1110

Depth

mm

580

580

580

580

580

Dimensions of cover Height

mm

28

28

28

28

28

Width

mm

650

650

650

1220

1220

Depth

mm

650

650

650

690

690

Weight

kg

26,0

26,0

27,0

59,0

59,0

Serial number

684...

687...

689...

698....

699...

Computerised part no.

1619290

1619300

1619320

1619330

1619340

1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air volume, 5m pipe length in combination with RXS 261H-1200H
2) Air inlet temperature TK 20°C outdoor temperature TK 7 °C, FK 6 °C, max. air volume, 5m pipe length in combination with RXS 261H-1200H
3) Distance 1 m free air

REMKO RXD

26