Troubleshooting and customer service

The equipment and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the
list below. For installations with an indoor unit and outdoor component, refer to the chapter "Troubleshooting
and customer service" in both manuals. Please inform your dealer if the unit is still not working correctly after all
the functional checks have been performed!

fault

Possible cause

Checks

Remedial measures

The unit does not start
or switches itself off

Power outage, undervoltage,

defective mains fuse / main circuit

breaker switched off

Are all other electrical installations

functioning correctly?

Check voltage, possible wait until

turned on again.

Damaged mains cable

Are all other electrical installations

functioning correctly?

Repair by a specialist

Waiting time after switch-on too short Have approx. 5 minutes

elapsed since the restart?

Schedule longer waiting periods

Temperature outside operating range.

Are the fans in the indoor unit

and outdoor component working

correctly?

Take into account the temperature

range for the indoor unit and outdoor

component

Overvoltages caused by thunder

storms

Has there recently been lightning?

Switch off the mains breaker and

switch it back on. Have it checked by

a specialist

Fault in external condensation pump

Did the pump shut down due to a

fault?

Check and if necessary clean the

pump

The unit does not respond
to the remote control

Transmission distance too far /

receiver affected by interference

Does the indoor unit beep when

pressing a button?

Reduce the distance to less than 6 m

or change position

Defective remote control

Is the unit running in manual mode?

Replace the remote control

Receiver or transmitter unit exposed

to excessive solar radiation

Does it function correctly in the

shade?

Place the receiver&transmitter unit in

the shade

Electromagnetic fields are interfering

with transmission

Does it function when switching off

possible sources of interference?

Signal is not transmitted when

interference sources are operational

Button in remote control jammed /

two buttons pressed at same time

Does the “Send” symbol appear on

the display?

Release the button / only press one

button

Batteries in remote control are flat

Have new batteries been inserted? Is

the display incomplete?

Insert new batteries.

The unit is running
but only provides
reduced cooling / heating
performance

Filter is unclean / air inlet / outlet

blocked by foreign items

Have the filters been cleaned?

Clean the filters

Windows and doors open. Heating/

cooling output increases

Have there been any constructional /

application-related changes?

Close windows and doors / install

additional units

Neither cooling nor heating mode has

been set

Does the cooling symbol appear on

the display?

Correct the settings for the unit

Fins on outdoor component blocked

by foreign items

Is the fan on the outdoor component

running? Are the fins unobstructed?

Check the fan or winter controller,

reduce the air resistance

Leaking refrigerant circuit

Are there signs of frost on the fins of

the indoor unit?

Repair by specialist

Outdoor component iced up

Check outdoor component. Has

the cassette sensor on the outdoor

component been correctly positioned?

De-ice and fit the sensor at the point

where the most ice forms

Condensation discharge

on unit

Drainage pipe on collection container

clogged / damaged

Can the condensation drain off

without any obstruction?

Clean the drainage pipe and collection

container

Faulty external condensation pump

or float

Is the collection tray full of water and

the pump not running?

Call out a specialist to replace the

pump

Condensation has not drained away

and has collected in the condensation

pipe

Is there a steady fall on the

condensation pipe? Check there is no

blockage in the pipe.

Ensure there is a fall when laying the

condensation pipe and clean the pipe.

Condensation does not drain off

Are the condensation pipes unblocked

and is there a steady fall? Are the

condensation pump and float switch

functioning correctly?

The condensation pipe must have

a fall. If necessary, clean the pipe. A

faulty condensation pump and float

switch should be replaced.

Float is stuck or jammed due to

excessive dirt.

Are the LEDs on the receiver unit of

the indoor unit flashing?

Should be cleaned by specialist firm

Malfunction

Icing up of

unit

In conjunction with RXM:

Heating/automatic mode set

Check mode setting

Set cooling mode

REMKO RXD

14