Remko rxd, Installation – REMKO RXD Series User Manual
Page 16
■
Service openings should be
provided in the suspended
ceiling to allow maintenance
access to the control box.
■
Any ventilation ducts or pipes
and connection fittings, which
are used to connect a second
room or supply fresh air, should
be insulated with diffusion-tight
material.
Installation material
The indoor unit is fastened using
4 threaded rods (provided by the
customer) at the side mounts.
In order to complete the
installation, wall plugs, trapezoidal
sheet metal supports, steel profiles,
fixing clamps for refrigerant and
condensation pipes (as well as
laying ducts) and connection
fittings for condensation pipes are
also required.
Selection of the installation
location
The indoor unit is designed
for horizontal mounting in
suspended ceilings with Euroraster
dimensions. It can also be installed
in other types of suspended
ceilings with different dimensions.
Take into account the installation
height of the equipment.
Minimum clearances
Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.
Installation
Installation should only be
performed by authorised
specialists.
NOTE
Unit installation
The unit is mounted face down
on four threaded rods. Take into
account the ceiling grid and any
other installations.
1. Use the dimensions of the
ceiling cassette to mark the
fixing points for the threaded
rods on structural parts
approved to support the static
load above the suspended
ceiling.
2. Fit any connection nozzles
before installing the unit
if connections to a second
room or a fresh air intake are
required.
See section Connections to
a second room or a fresh air
intake.
3. Fit the indoor unit onto the
threaded rods and use the
lower nuts to level the unit
(Fig 5 and 6)
.
Minimum clearances
All values in mm
300
300
300
300
300
300
300
300
300
300
REMKO RXD
16