Remko aty, Condensation connection – REMKO ATY 261 User Manual
Page 20
Condensation connection
If the temperature falls below the
dew point, condensation will form
on the vaporiser of the indoor unit
during cooling.
The collection tray below the
vaporiser should be connected to
the drain.
■
The condensation pipe should
have a fall of min. 2 %. This
is the responsibility of the
customer.(Fig 10). If necessary,
fit vapour diffusion tight
insulation.
■
The condensation pipe from
the unit should run freely
into the drainage pipe. If the
condensation runs directly
into a sewer pipe, fit a trap to
prevent any unpleasant odours.
■
When operating the unit at
outdoor temperatures below
0 °C, ensure the condensation
pipe is laid to protect it
against frost. If necessary, fit
supplementary pipe heating.
■
Once the pipe has been laid,
check the condensation drains
off and permanently seal it.
The standard condensation hose is
for connection to the left or right
side (as viewed from the front).
Remove the plug when making the
connection.
10
Condensation connection
at least
2% fall
Condensation connection
right or left
Condensation connection
for indoor unit
40
45
65
50
The condensation pump
cannot be built into the unit.
NOTE