Error F5: Condenser fan speed not alright
Shut off the power supply and turn it on 5
seconds later. Is it still displaying the error
code?
NO
The unit operates normally.
YES
Shut off the power sopply, rotate the cross
fan by hand. Does it rotate properly?
NO
Disassembly the connection
between fan and motor,
check if the bearing is
normal?
YES
YES
NO
Check the wires of fan motor. Are all the
connections good?
NO
Correct the
connections.
Replace
indoor fan
motor.
Replace the
bearing.
YES
3
NO
Replace
indoor fan
motor.
YES
4
NO
5
YES
6
REMKO BL...DC
44
This manual is related to the following products:
See also other documents in the category REMKO Conditioners:
- RKL 491 DC S-LINE (28 pages)
- RKL 360 S-LINE (28 pages)
- MKT 291 S-LINE (28 pages)
- ML 523 DC (64 pages)
- MXD 522 (48 pages)
- MXW 522 (44 pages)
- PWL 303 HK (24 pages)
- RVT 683 DC (72 pages)
- WLT 85 (24 pages)
- RVS 150 H (44 pages)
- KWL Series (48 pages)
- MKT 240 (12 pages)
- MKT 250 (12 pages)
- MKT 260 (16 pages)
- RKL 350 (16 pages)
- MKT 290 (20 pages)
- RKL 480 (16 pages)
- RKL 240 (16 pages)
- RKL 490 DC (20 pages)
- ATY 351 (28 pages)
- ATY 350 (32 pages)
- ATY 351 DC (36 pages)
- MD 351 (32 pages)
- ML 280 (24 pages)
- BL 351 (32 pages)
- ML 522 DC (32 pages)
- MVT 1050 DC (28 pages)
- MXD 520 v.3 (28 pages)
- MXD 520 v.1 (28 pages)
- RKS 448 H (20 pages)
- RKS 524 H (16 pages)
- RKS 371 H (28 pages)
- RKV 24 W (20 pages)
- RKV 24 T (20 pages)
- RKV 24 C (24 pages)
- RKW INOX (28 pages)
- RVD 521 DC (32 pages)
- RM Series (36 pages)
- RVD xxx DC (52 pages)
- RWH 680 (20 pages)
- RVT 521 DC (32 pages)
- RXS xxx H (20 pages)
- RXD Series (28 pages)
- RXW 480 (20 pages)