5.6 Oil return measures

If the outdoor unit is installed at a higher level than

the indoor unit, suitable oil return measures must

be taken. Usually, an oil pump bend is installed for

every 2.5 metres of height difference.

2

1

A

B

3

Fig. 28: Oil return measures

A: Outdoor unit

B: Indoor unit

1: One oil pump bend in suction pipe to outdoor

unit every 2.5 metres of height difference

2: Radius: 50mm

3: Max. 10m

5.7 Connection variants for the

indoor unit

The following connection variants can be used for

the refrigerant, condensate and control lines.

A

C

B

Fig. 29: Connection variants

A: Outlet on the wall, right

B: Outlet through the wall, right

C: Outlet on the wall, left

5.8 Wall bracket for the indoor unit

A

B

C

D

F

I

J

Fig. 30: Mounting points for wall bracket BL 262-352 DC IT (Front view, all dimensions in mm)

Unit type / dim. in mm

A

B

C

D

F

I

J

BL 262 DC IT

375

375

275

165

45

346

100

BL 352 DC IT

417.5

417.5

230

210

45

315

100

The diameter of the pipe break-through is 65 mm for all units types.

The wall bracket for the units must be attached with suitable screws and anchors.

25