REMKO BL 262 DC User Manual
Page 43
Error EC: Refrigerant leakage detection
Shut off the power supply and turn it on 5 sec-
onds later. Is it still displaying the error code?
YES
Is there cool air blowing out from indoor air
outlet?
YES
Check if T2 sensor is well fixed. Correct the
installation or replace T2 sensor. Does the
problem remain again?
NO
YES
Is there any leakage? Especially the connec-
tions parts, such as the gas valve and the liquid
valve.
Replace indoor PCB.
YES
Repair the leakage and recharge the refrig-
erant.
NO
Is there any blocking? (such as the capillary or
the welded points of the pipes).
YES
Clear the blocking.
43
This manual is related to the following products:
See also other documents in the category REMKO Conditioners:
- RKL 491 DC S-LINE (28 pages)
- RKL 360 S-LINE (28 pages)
- MKT 291 S-LINE (28 pages)
- ML 523 DC (64 pages)
- MXD 522 (48 pages)
- MXW 522 (44 pages)
- PWL 303 HK (24 pages)
- RVT 683 DC (72 pages)
- WLT 85 (24 pages)
- RVS 150 H (44 pages)
- KWL Series (48 pages)
- MKT 240 (12 pages)
- MKT 250 (12 pages)
- MKT 260 (16 pages)
- RKL 350 (16 pages)
- MKT 290 (20 pages)
- RKL 480 (16 pages)
- RKL 240 (16 pages)
- RKL 490 DC (20 pages)
- ATY 351 (28 pages)
- ATY 350 (32 pages)
- ATY 351 DC (36 pages)
- MD 351 (32 pages)
- ML 280 (24 pages)
- BL 351 (32 pages)
- ML 522 DC (32 pages)
- MVT 1050 DC (28 pages)
- MXD 520 v.3 (28 pages)
- MXD 520 v.1 (28 pages)
- RKS 448 H (20 pages)
- RKS 524 H (16 pages)
- RKS 371 H (28 pages)
- RKV 24 W (20 pages)
- RKV 24 T (20 pages)
- RKV 24 C (24 pages)
- RKW INOX (28 pages)
- RVD 521 DC (32 pages)
- RM Series (36 pages)
- RVD xxx DC (52 pages)
- RWH 680 (20 pages)
- RVT 521 DC (32 pages)
- RXS xxx H (20 pages)
- RXD Series (28 pages)
- RXW 480 (20 pages)