3 performance curves for heating and cooling – REMKO BL 262 DC User Manual
Page 11
2.3 Performance curves for heating and cooling
Heating capacity BL 262 DC
0,00
1,00
2,00
3,00
4,00
5,00
12
7
2
0
-7
-10
-15
2
1
3
A
[°C]
Fig. 3: Performance curves, heating BL 262 DC (data for 20 °C indoor temperature)
A: Outside temperature
1: COP
2: Heating capacity in kW
3: Power consumption in kW
Outside temperature in °C
12
7
2
0
-7
-10
-15
Heating capacity in kW
3.33
2.93
2.79
2.65
2.36
2.22
1.91
Power consumption in kW
0.76
0.75
1.26
1.19
1.11
1.11
1.05
COP
4.37
3.91
2.21
2.23
2.12
2.00
1.82
Cooling capacity BL 262 DC
0,00
1,00
2,00
3,00
4,00
5,00
6,00
21
25
30
35
40
45
50
2
1
3
A
[°C]
Fig. 4: Performance curves, cooling BL 262 DC (data for 27/19 °C indoor temperature)
A: Outside temperature
1: EER
2: Cooling capacity in kW
3: Power consumption in kW
Outside temperature in °C
21
25
30
35
40
45
50
Cooling capacity in kW
2.80
2.99
3.01
2.90
2.49
2.36
2.30
Power consumption in kW
0.57
0.61
0.67
0.73
0.74
0.75
0.78
EER
4.93
4.87
4.51
3.97
3.36
3.13
2.94