beautypg.com

3 performance curves for heating and cooling – REMKO BL 262 DC User Manual

Page 11

background image

2.3 Performance curves for heating and cooling

Heating capacity BL 262 DC

0,00

1,00

2,00

3,00

4,00

5,00

12

7

2

0

-7

-10

-15

2

1

3

A

[°C]

Fig. 3: Performance curves, heating BL 262 DC (data for 20 °C indoor temperature)

A: Outside temperature

1: COP

2: Heating capacity in kW

3: Power consumption in kW

Outside temperature in °C

12

7

2

0

-7

-10

-15

Heating capacity in kW

3.33

2.93

2.79

2.65

2.36

2.22

1.91

Power consumption in kW

0.76

0.75

1.26

1.19

1.11

1.11

1.05

COP

4.37

3.91

2.21

2.23

2.12

2.00

1.82

Cooling capacity BL 262 DC

0,00

1,00

2,00

3,00

4,00

5,00

6,00

21

25

30

35

40

45

50

2

1

3

A

[°C]

Fig. 4: Performance curves, cooling BL 262 DC (data for 27/19 °C indoor temperature)

A: Outside temperature

1: EER

2: Cooling capacity in kW

3: Power consumption in kW

Outside temperature in °C

21

25

30

35

40

45

50

Cooling capacity in kW

2.80

2.99

3.01

2.90

2.49

2.36

2.30

Power consumption in kW

0.57

0.61

0.67

0.73

0.74

0.75

0.78

EER

4.93

4.87

4.51

3.97

3.36

3.13

2.94

11