2 diagnosis and solution indoor unit, Remko bl...dc – REMKO BL 262 DC User Manual
Page 40
Malfunction on the indoor unit
Indica-
tion
Cause
Required action
E0
EEPROM error
See error analysis
E1
Communication error between outdoor and
indoor unit
Contact specialist dealer
E2
Phase monitoring has responded
Check wiring
E3
Evaporator fan motor speed too low / defective See error analysis
E4
Ambient air probe on indoor unit defective /
connection interrupted (T1)
Check connection and plug
E5
Register probe on indoor unit defective /
connection interrupted (T2)
Check connection and plug
EC
Cooling mode: no cooling output after 30 min.
Heating mode: no heating output after 30 min.
Contact specialist dealer
F1
Ambient air probe for outdoor unit faulty /
connection interrupted (T4)
Check connection and plug
F2
Register probe on outdoor unit defective /
connection interrupted (T3)
Check connection and plug
F3
Heat gas probe on outdoor unit faulty /
connection interrupted (T5)
Check connection and plug
F4
EEPROM error on outdoor unit
Switch off power to unit for 1 min.
Contact specialist dealer.
F5
Condenser fan speed not alright
See error analysis
P0
Rotational speed monitoring on compressor
has responded (inverter module)
Check connections CN4 and CN1 on the out-
door unit PCB / Contact specialist dealer
P1
Overload switch on outdoor unit tripped (250V) Check the voltage of the power supply
P2
Excessive temperature (Klixon) compressor
has tripped
Check the refrigerant quantity / Check the
resistance of the compressor sensor (normal
0Ω)
P3
Compressor overcurrent protection
has responded
Check winding resistance of the compressor
(1Ω = U-V / U-W / V-W)
11.2 Diagnosis and solution indoor unit
Error E0: EEPROM parameter error
Shut off the power supply and turn it on 5 sec-
onds later. Is it still displaying the error code?
YES
Is the EEPROM chip plugged in PCB well?
NO
Correct the connection.
YES
Replace the ind.
REMKO BL...DC
40