Fig. 36: Installation on the outdoor unit

Fig. 37: Installation on the indoor unit

6.

Then tighten the fittings with 2 appropriately-

sized open-ended spanners. Use one

spanner to counter the force when tightening

the fitting (Fig. 38).

2

1

Fig. 38: Tightening the fitting

1: Tighten with the first open-ended spanner

2: Counter with the second open-ended spanner

7.

Open the stop cocks with an Allen key before

switch the system on!

Pipe dimension in

inches

Tightening torque in Nm

1/4"

15-20

3/8"

33-40

1/2"

50-60

5/8"

65-75

3/4"

95-105

CAUTION!

Only open the stop cocks following complete

installation of the quick-release couplings and

before switching the system on!

6.4 Leak testing

Once all the connections have been made, the

pressure gauge station is attached to the Schrader

valve as follows (if fitted):

red = small valve = high pressure

blue = large valve = suction pressure

Leak testing involves spraying a leak detection

spray onto the connections. If bubbles are visible,

the connections have not been made properly.

Then tighten the screw connection.

NOTICE!

The escape of refrigerant contributes to cli-

matic change. In the event of escape, refrig-

erant with a low greenhouse potential has a

lesser impact on global warming than those

with a high greenhouse potential. This device

contains refrigerant with a greenhouse poten-

tial of 1975. That means the escape of 1 kg of

this refrigerant has an effect on global warming
that is 1975 times greater than 1 kg CO

2

,

based on 100 years. Do not conduct any work

on the refrigerant circuit or dismantle the

device - always enlist the help of qualified

experts.

REMKO BL...DC