Wiring, Two modulating valves staged - stand-alone wiring, Modgas-xwr technical guide – Orion System MODGAS-XWR User Manual
Page 7

MODGAS-XWR Technical Guide
WIRING
7
Fan Enable
Low Speed Fan
See
For SAT OPTIONS Jumper Settings
Only One Supply Air Temperature Sensor
Can Be Used Per Application.
Table 8, Page 26
Connect SAT
Input to Reheat
Board’s SAT
Input if Applicable.
See Table 7,
Page 26.
YS102530 REV 1
GAS
V
ALVE
2
GAS
V
AL
V
E
1
PO-IGN2
PO-IGN1
COMMON
RLY4
RLY3
RLY2
RLY1
WATTMASTER
CONTROLS
MADE IN USA
AUX BIN
HEAT EN
RESET IN
OPTIONS
SAT
GND
AUX AIN
GND
STATUS
ALARM
COMM
POWER
ANODE
AN
OD
E
AN
O
D
E
M
ENTER
UP
DOWN
ALARM
MENU
OE377-26-00060
MODGAS-XWR
AAON No.: V20780
WattMaster No:
#SW000055
Rev.: 1A
E-BUS
CONNECT
I2C
CONNECT
+24
V
AC
GND
CONTACT RATING
IS 1 AMP MAX
@ 24 VAC
HEAT 1
LOW SPEED
FAN
PROOF OF IGNITION 1
PROOF OF IGNITION 2
GAS VALVE 2
GAS VALVE 1
GAS
V
AL
VE
TERMINALS
HEAT 2
COMMON
RELAY OUTPUT
TERMINALS
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET INPUT (AI)
SAT INPUT (AI)
GND(AI)
GND
AUX. (AI)
www.aaon.com
MODGAS-XWR CONTROLLER
(OE377-26-00060)
Modulating
Gas Valve 1
Proof of Ignition
Signal 1 (24 VAC)
Modulating
Gas Valve 2
Proof of Ignition
Signal 2 (24 VAC)
EBC-E-BUS Cable
Can Connect To
12 Relay E-BUS
Expansion
Port
0-10VDC
External
Reset Signal
Heat Enable
Signal
(24VAC)
W1
Heat Valve 1
Heat Valve 2
Check Your Fan
Relay Wiring (RLY1)
Schematic For
Proper Wiring.
Two Modulating Valves Staged - Stand-Alone Wiring
Figure 4: Two Modulating Valves Staged Stand-Alone Wiring Diagram
Two Modulating Valves Staged -
Stand-Alone Wiring
This configuration operates as Stand-Alone (Figure 4, below) or
communicating with an AAON Unit Controller (Figure 8, page 11).
If using an MHGRV-X Controller along with the MODGAS-XWR
Controller in Stand-Alone, the SAT Sensor always attaches to the
MODGAS-XWR Controller.
NOTE: Up to 12 fi xed stages can be added by using the 12-Relay
E-BUS Expansion Module. (Figure 5, page 8).
WARNING: Do Not Connect Power To VOUT/Ground
Terminal
Block!