MODGAS-XWR Technical Guide

OVERVIEW

3

General Information

YS102530 REV 1

GAS

VAL

V

E

2

GAS

VAL

V

E

1

PO-IGN2

PO-IGN1

COMMON

RLY4

RLY3

RLY2

RLY1

WATTMASTER

CONTROLS

MADE IN USA

AUX BIN

HEAT EN

RESET IN

OPTIONS

SAT

GND

AUX AIN

GND

STATUS

ALARM

COMM

POWER

ANODE

AN
O

D

E

AN
O

D

E

M

ENTER

UP

DOWN

ALARM

MENU

OE377-26-00060

MODGAS-XWR

AAON No.: V20780

WattMaster No:

#SW000055

Rev.: 1A

E-BUS

CONNECT

I2C

CONNECT

+24

V

AC

GND

CONTACT RATING

IS 1 AMP MAX

@ 24 VAC

HEAT 1

LOW SPEED

FAN

PROOF OF IGNITION 1

PROOF OF IGNITION 2

GAS VALVE 2

GAS VALVE 1

GAS

V

AL

VE

TERMINALS

HEAT 2

COMMON

RELAY OUTPUT

TERMINALS

INPUT TERMINALS (TYPE)

HEAT ENABLE (BI)

AUX. (BI)

GND

RESET INPUT (AI)

SAT INPUT (AI)

GND(AI)

GND

AUX. (AI)

www.aaon.com

MODGAS-XWR CONTROLLER

(OE377-26-00060)

Figure 1: OE377-26-00060 MODGAS-XWR Controller

Features

The

MODGAS-XWR Controller

provides the following:

Can control two (2) Gas Valves using input from
Proof of Ignition Modules

Up to four (4) MODGAS-XWR Modules can be daisy-
chained together to control up to eight (8) Modulation Gas
Valves

Monitors Supply Air Temperature and Supply Air Reset
and modulates gas valves to maintain Setpoint

Provides active relays to control the Fan and
Heat Stages

Contains a 2 x 8 LCD character display and 4 buttons
that allow for status display, setpoint changes, and
confi guration changes

NOTE: The

MODGAS-XWR Controller

contains no user-

serviceable parts. Contact qualifi ed technical personnel
if your

MODGAS-XWR Controller

is not operating

correctly.

Overview

The OE377-26-00060 MODGAS-XWR Controller (AAON Part No.
V20780) is designed to modulate up to two (2) gas valves to maintain
a desired Discharge Air Temperature. The MODGAS-XWR Control-
ler also controls the speed of the induced draft fan to maintain proper
combustion in the heat exchanger. See Figure 1.

The controller can be used as a stand-alone unit or be connected to
a VCM-X E-BUS Controller (OE332-23E-VCMX; AAON Part No.
V07150), VCB-X Controller (OE335-26B-VCBX; AAON Part No.
V28940), VCC-X Controller (OE338-26B-VCCX; AAON Part No.
V42430), or 12 Relay E-BUS Expansion Module (OE358-23E-12R;
AAON Part No. R69180) using a modular cable.

The MODGAS-XWR Controller can be confi gured at the factory for one
(1) modulating valve, two (2) staged modulating valves, or one (1) modu-
lating with multiple fi xed staged valves (stand-alone operation only).

When using the MODGAS-XWR Controller to replace an existing
MODGAS II Controller, see Appendix B, page 27 for details.