APPENDIX A

25

Supply Air Temperature Sensor Installation

Mounting the Supply Air Temperature

Sensor

The Supply Air Temperature (SAT) Sensor should be

located in the duct-work downstream of the unit supply

air

connection.

Locate the sensor in the center of the widest part of the

duct. Use the supplied template and a 5/16” drill to make

a hole for the sensor.

Install the gasket over the probe and mount securely to

the duct using the supplied sheet metal screws. Be sure

the gasket is compressed to provide an air tight seal.

For best accuracy, apply insulation on the outside of the

duct, over the sensor. This will help prevent thermal

gradients from affecting the sensor.

WARNING: Make sure your Supply Air Temperature

Sensor is mounted and wired according to

these instructions prior to testing the unit or

else the modulating valve will not control

properly and may damage your equipment.

Figure 11: Supply Air Temperature Sensor Installation

Leads Are Non-Polarized. Butt Splice Leads
To 24 Gauge Wire Minimum.

In Stand Alone Applications And In Retrofit
Applications, Connect Leads to “SAT” And “GND” On
MODGAS-XWR Controller. See

.

If Using A VCM-X Or VCB-X Controller, Connect Leads
To “AI2” And “GND” On Main Controller.

Table 7, Page 26

Stand-Alone Mode

In Stand-Alone Mode, the SAT Sensor is connected to the MODGAS-
X Controller. If, in Stand-Alone Mode, the MODGAS-X Controller is
used in conjunction with a Stand-Alone MHGRV Controller, the SAT
sensor is shared between the two controllers and always attaches to the
MODGAS-X Controller.

See Table 8, page 26 for SAT Options Jumper Settings and see Figures
2, 4, 5 & 6
for wiring. See Table 7, page 26 for details about retrofi t
applications.

Communication Mode

When communicating with AAON Unit Controllers, the SAT Sensor
will be connected to the Main Controller. The exception would be in
retrofi t applications with older controllers. See Table 9, page 26 for SAT
Options Jumper Settings and see Figures 3 & 7 for wiring. See Table
7
, page 26 for details about retrofi t applications.