Lcd display screens, Force valve & confi guration screens, Modgas-xwr technical guide 18 – Orion System MODGAS-XWR User Manual
Page 18: Force valve screens, Confi guration screens
LCD DISPLAY SCREENS
MODGAS-XWR Technical Guide
18
Force Valve & Confi guration Screens
Force Valve Screens
Refer to the following map when navigating through the Force Valve
Screens. From the FORCE VALVE Screen, press
. At the
V1 and V2 FORCE ON/OFF screens, press the
arrow key to
turn the FORCE MODE on and press the
arrow key to turn
the FORCE MODE off. Use the
and
arrow keys to
increase and decrease the percentage.
FORCE
VALVES
V1 FORCE
ON/OFF
FORCE V1
X%
FORCE VALVE 1 PERCENTAGE
This screen only appears when Valve 1 Force is on.
This screen below will appear when the Force Mode times out after 1
hour.
FORCE
TIMEOUT
Press the
button to turn the Force Mode off.
Press the
button to decrease the percentage.
NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.
FORCE MODE TIME OUT
V2 FORCE
ON/OFF
FORCE V2
X%
FORCE VALVE 2 PERCENTAGE
This screen only appears when Valve 2 Force is on.
Press the
button to turn the Force Mode off.
Press the
button to decrease the percentage.
NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.
Confi guration Screens
Refer to the following map when navigating through the Confi guration
Screens. From the CONFIG Screen, press
to scroll through
the screens and change setpoints. Use the
and
arrow
keys to change your selections. Press
to save any changes.
CONFIG
# STAGES
1 TO 15
NUMBER OF TOTAL STAGES
Range is 1 to 15. Default is 2.
# MOD STG
1 OR 2
NUMBER OF MODULATING STAGES
Range is 1 or 2. Default is 2.