beautypg.com

Lcd display screens, Alarm & setpoint screens, Modgas-xwr technical guide – Orion System MODGAS-XWR User Manual

Page 17: 17 alarm screens, Setpoint screens

background image

MODGAS-XWR Technical Guide

LCD DISPLAY SCREENS

17

Alarm Screens

Refer to the following map when viewing Alarm Screens. These screens
will display automatically when alarms are present. For more informa-
tion, see pages 20-22.

ALARMS

ALARMS

The alarms are as follows:

NO ALARMS:

This will be shown if there are no current alarms.

V1 NOT DETECTED:

Gas Valve 1 is not detected.

V2 NOT DETECTED:

Gas Valve 2 is not detected.

V1 NO PROOF OF FLAME:

No Proof of Flame Ignition Module input

is detected..

V2 NO PROOF OF FLAME:

No Proof of Flame Ignition Module input

is detected.

SAT CUTOFF:

This indicates a Supply Air Temperature Cutoff Alarm

condition which is activated if the SAT has risen above 200ºF. The alarm
will go away if after a fi xed delay period the SAT has dropped below
200ºF.

SAT FAILURE:

The Supply Air Temperature sensor has been discon-

nected for more than 60 seconds. This alarm will be disabled when the
sensor is reconnected.

COMM T/O ERROR:

Communications have been lost with the main

controller. This alarm will disable when communications resume.

Alarm & Setpoint Screens

Setpoint Screens

Refer to the following map when navigating through the Set-
point Screens. From the SETPOINT Screen, press

to

scroll through the screens and change setpoints. Use the

and

arrow keys to change your selections. Then press

to save the new setpoint.

WARNING: The

key must be pressed after

changing setpoints for your entries to be saved

for subsequent power-ups.

NOTE: When the MODGAS-XWR is operating in Communi-

cations Mode, these setpoints screens will not appear
on the LCD display because they are controlled by the
Main Controller.

SETPOINT

SAT SP

40-150°F

4-65°C

RESET SP

40-150°F

4-65°C

HEATING SUPPLY AIR TEMPERATURE SETPOINT

This is the target temperature while the heating is enabled. If you are
using the reset signal, this is the setpoint it will calculate to at zero volts.
The Setpoint Screen will display only in stand-alone mode.

Minimum

Default

Maximum

40°F

4°C

120°F

49°C

150°F

65°C

RESET HEATING SUPPLY AIR SETPOINT

This is maximum temperature at which the Supply Air Temperature will
reset to. The Setpoint Screen will display only in stand-alone mode.

Minimum

Default

Maximum

40°F

4°C

120°F

49°C

150°F

65°C