TROUBLESHOOTING

MODGAS-XWR Technical Guide

22

Troubleshooting Alarms

Mechanical Failure:

Check relay outputs on the MODGAS-XWR for 24

VAC

output.

Verify the SAT OPTIONS jumper settings on the

MODGAS-XWR for Supply Air Temperature Sensor.

Verify gas valve LED is solid. Try forcing valves (refer

to Force Screens in this guide).

Verify that the Supply Air Temperature Sensor is

connected to SAT and GND on the MODGAS-XWR

(stand-alone mode) or to AI2 and GND on the Main

Controller (communicating mode).

Verify Supply Air Temperature Sensor probe is

mounted correctly in supply duct.

Remove SAT and GND wiring from the MODGAS-

XWR and ohm sensor out (this may indicate open or

failed wiring). Refer to chart in back of this guide for

readings.

Supply Air Temperature Failure:

Verify that the Supply Air Temperature Sensor is

connected to the SAT and GND on the MODGAS-

XWR (stand-alone mode) or to AI2 and GND on the

Main Controller (communicating mode).

Remove SAT and GND wiring from MODGAS-XWR

and ohm sensor out (this may indicate open or failed

wiring). Refer to chart in back of this guide for

readings.

Verify the SAT OPTIONS jumper settings on the

MODGAS-XWR for the Supply Air Temperature

Sensor.

SAT Cutoff Mode:

Remove SAT and GND wiring from the MODGAS-

XWR and ohm sensor out (this may indicate open or

failed wiring). Refer to chart in back of guide for

readings.

With Supply Air Sensor disconnected from the

MODGAS-XWR, set volt meter to DC volts and

measure voltage between SAT and GND on board.

Refer to chart in back of this guide for readings.

Verify Supply Air Temperature Sensor reading in duct

with 3rd party temperature testing device.

Communications Loss:

Check COMM LED on MODGAS-XWR.

Verify 24 VAC power to all interconnected WattMaster

controllers.

Verify E-BUS connection between the MODGAS-

XWR and associated WattMaster controllers.

In communication mode (connected to an AAON unit

Controller with modular cable), confi rm that Main

MODGAS screens shows COMM MODE that Main

Controller’s MODGAS status screen displays

MODGAS-XWR’s Position %.

Troubleshooting Alarms