APPENDIX A

MODGAS-XWR Technical Guide

26

SAT Sensor Wiring Guide & Jumper Settings

SAT Options Jumper Settings

Refer to Tables 8 & 9 to determine the settings. See Figure 2, page 5
for jumper locations.

STAND-ALONE MODE

SAT OPTIONS JUMPER SETTINGS*

CONDITION

SETTING

MODGAS-XWR Only

1

MODGAS-XWR with

MHGRV-X**

1

MODGAS-XWR with

MHGRV II***

2

MODGAS-XWR with

MHGRV III

2

* For SAT Sensor testing, use Table 5, page 23 for
jumper setting 1 and Table 6, page 24 for jumper
setting 2.

** In this situation, also set MHGRV-X SAT Option
to MODGAS-X. See the MHGRV-X Technical
Guide
for more information.

*** The MHGRV II must have PU resistor installed.

Table 8: Stand-Alone Mode SAT OPTIONS Jumper
Settings

SAT Wiring Conditions

MODGAS-XWR ONLY

MHGRV-X ONLY

MODGAS-XWR & MHGRV-X

STAND-

ALONE

Install Supply Air
Sensor in MODGAS-
XWR.

Install Supply Air
Sensor in MHGRV-X.
Set “SAT Options”
Jumpers to “Normal”.

Install Sensor in MODGAS-XWR and daisy-chain
it to the MHGRV-X. Set “SAT Options” Jumpers to
“MODGAS X”. If connected to a MODGAS II
Retrofi t, Set “SAT Options” Jumpers to “MODGAS”.

VCB-X,

VCC-X

Install Supply Air Sensor
in VCB-X or VCC-X.
Connect to VCB-X or
VCC-X using E-BUS
cable.

Install Supply Air
Sensor in VCB-X or
VCC-X. Connect to VCB-X
or VCC-X using E-BUS
cable.

Install Supply Air Sensor in VCB-X or VCC-X.
Connect to VCB-X or VCC-X using E-BUS cable.

VCM-X,

SA, RNE

Install Supply Air Sensor
in Main Controller.
Connect to Main
Controller using I

2

C

cable.

Install Supply Air
Sensor in Main Controller.
Connect to Main
Controller using I

2

C cable.

Install Supply Air Sensor in Main Controller.
Connect to Main Controller using I

2

C cable.

VCM,

VAV/CAV,

MUA,

MUA II,

MUA IID

Install Supply Air Sensor
in MODGAS-XWR.
Connect to Main
Controller using I

2

C

cable.

Install Supply Air
Sensor in MHGRV-X.
Connect to Main
Controller using I

2

C cable.

Install Supply Air Sensor in MODGAS-XWR.
Connect to Main Controller using I

2

C cable.

Table 7: SAT Wiring Conditions

COMMUNICATIONS MODE

SAT OPTIONS JUMPER SETTINGS*

CONDITION

SETTING

VCM-X / RNE / SA*

1

VCM, MUA, MUA II,

MUA IID VAV/CAV**

1

VCB-X / VCC-X*

1

* For SAT Sensor testing, use Table 5, page 23 for
jumper setting 1. SAT should be connected to the
Main Controller.

** For SAT Sensor testing, use Table 5, page 23
for jumper setting 1. SAT should be connected to
the MODGAS-X Controller.

Table 9: Communications Mode SAT OPTIONS
Jumper Settings