Module wiring & connections, Vcm-x component & systems wiring, When used with orion vcm-x e-bus controller – Orion System VCM-X E-BUS Component User Manual
Page 99: Head pressure transducers, Hssc cable connect to vcm-x e-bus, Filename date: s. olson description: page drawn by

VCM-X Component & Systems Wiring
Module Wiring & Connections
99
HP2C2 Controller Wiring When Used With The VCM-X E-BUS
Figure 75: OE370-23-HP2C2 Two Condenser Head Pressure Module to VCM-X E-BUS Controller Wiring
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
DRAWN BY:
When Used With Orion VCM-X E-BUS Controller
JOB NAME
06/05/15
HP2C2-1A.CDR
Two Condenser Head Pressure Module Wiring
1
Wiring For Two Condenser Head Pressure Module When Used With Orion VCM-X E-BUS Controller
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
SIG
GND
+V
BK
RD
WH
Head Pressure
Transducers
OE370-23-HP2C2
Two Condenser
Head Pressure II Module
OPTIONS Dip Switch Setting
Not Required When Connected
To VCM-X E-BUS
+5V
SIG 2
GND
OP
T
IO
N
S
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
GND
R1
R2
GND
RELAYS
SIG 3
+5V
GND
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
PWR
Connect To Other
WattMaster-Approved
E-BUS Expansion
Module(s)
HSSC Cable
24 VAC Transformer
3 VA Minimum
Line Voltage
24 V
A
C
GND
WARNING!! Observe
Polarity! All boards must
be wired with GND-to-
GND and 24 VAC-to-24
VAC.
NOTE:
NORMALLY OPEN AND
RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
ALL RELAY OUTPUTS
ARE
HSSC Cable
Connect To
VCM-X E-BUS
Set ADDRESS Dip Switch 1 to ON for Water
Cooled or to OFF for Air Cooled. Currently
showing OFF for Air Cooled.
Set ADDRESS Dip Switch 2 to OFF on all
communicating applications unless it is
intended to be the Second Head Pressure
Module on a system. If set to ON, it will not
communicate. Currently showing OFF.
Set ADDRESS Dip Switch 3 to ON to
disable Circuit B alarms when only one
Condenser is Used. Currently showing OFF.
Set ADDRESS Dip Switch 4 to OFF to make
reversing valve "ON to Heat / OFF to Cool.”
Set to ON to make reversing valve “ON to
Cool / OFF to Heat.” Currently showing OFF.
ADDRESS
BIN 1
BIN 2
BIN 3
COM
+24 Volts
Condenser Fan A
ECM Motor
Duty Cycle
Condenser Fan B
ECM Motor
COM
+
Condenser
Signal B
COM
+
Condenser
Signal A
CONDENSER A ENABLE
R1
R3
CONDENSER B ENABLE
COMM
REVERSING VALVE B ENABLE
REVERSING VALVE A ENABLE
R4
R2
YELLOW
BLUE +24 OUT
+24 Volts
Duty Cycle
YELLOW
BLUE +24 OUT
LED BLINK CODES
LED NAME
STAT
BLINKS QTY. OF SENSORS INSTALLED
LED NAME
ALARM
NO PROBLEMS
0
NO SENSORS DETECTED
1
HIGH HEAD PRESSURE DETECTED
2
LOW HEAD PRESSURE DETECTED
3
WattMaster Label
#LB102110-A
Rev.: 1A
E-BUS
Connector
E-BUS
Connector
+5V
SIG 1
GND
+5V
SIG 2
GND
+5V
SIG 3
GND
+5V
SIG 4
GND
+24
VAC
GND
BIN 1
BIN 2
BIN 3
COM
HEAD
PRESSURE
TRANSDUCER #1
HEAD
PRESSURE
TRANSDUCER #2
HEAD
PRESSURE
TRANSDUCER #3
HEAD
PRESSURE
TRANSDUCER #4
REV. VLV. ENABLE INPUT
COMMON
PWM2+
AAON No.:
V20660
AO1
AO2
GND
COND. A ENABLE INPUT
COND. B ENABLE INPUT
COND. A SIGNAL
COND. B SIGNAL
PWM1-
PWM1+
PWM2-
COND. FAN A
COND. FAN B
COND. FAN A
COND. FAN B
GND
Two Condenser Head Pressure II Module
2C2
Orion No.:OE370-23-HP
www.aaon.com
RELA
Y
C
ONT
A
CT
RA
TING
IS
1
A
MP
MAX
@
24
V
A
C
COND. A ENABLE
COND. B ENABLE
REV. VLV. A ENABLE
REV. VLV. B ENABLE
R1
R2
R3
R4
RC
RELAY COMMON
A1
A2
B1
B2