Miscellaneous diagrams and technical information, Vcm-x component & systems wiring 109, Hvac – Orion System VCM-X E-BUS Component User Manual
Page 109: When used with orion vcm-x e-bus controller, Aaon wshp-x2 wiring - dual circuit 2, Hssc cable, 24 vac, Filename date: s. olson description: page drawn by
VCM-X Component & Systems Wiring
109
Miscellaneous Diagrams and Technical Information
Figure 85: OE334-26-WSHP-X2 WSHP-X2 Controller Dual Circuit Wiring to VCM-X E-BUS Controller
WSHP-X2 Controller Wiring When Used With The VCM-X E-BUS
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
DRAWN BY:
When Used With Orion VCM-X E-BUS Controller
JOB NAME
06/05/15
WSHPX2-Wr1-2.CDR
AAON WSHP-X2 Wiring - Dual Circuit
2
Wiring For WSHP-X2 When Used With Orion VCM-X E-BUS Controller
Connect To Other
WattMaster-Approved
E-BUS Expansion
Module(s)
WARNING!! Observe
Polarity! All boards must
be wired with GND-to-
GND and 24 VAC-to-24
VAC. Failure to observe
polarity could result in
damage to the boards.
HSSC Cable
WATTMASTER CONTROLS
Y 102374 REV 0
S
MADE IN USA
OE334-26-WSHP-X2
Water Source
Heat Pump X2 Module
NOTE:
NORMALLY OPEN AND
RATED FOR 24 VAC POWER
ONLY
ALL RELAY OUTPUTS
ARE
COMP. A2 ENABLE
COMP. A1 ENABLE
R1
R4
R5
R3
R2
COMM
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
HVAC
24 VAC
GND
T1
WATER POF A
BIN6
COM
E
LEAVING WATER
TEMPERATURE
FOR SYSTEM A
T2
BIN7
WATER POF B
SIG 2
GND
+V
BK
RD
WH
SIG 1
GND
+V
BK
RD
WH
CIRCUIT A1
SUCTION PRESSURE
TRANSDUCER
SIG 2
GND
+V
BK
RD
WH
SIG 1
GND
+V
BK
RD
WH
CIRCUIT A2
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B1
SUCTION PRESSURE
TRANSDUCER
CIRCUIT B2
SUCTION PRESSURE
TRANSDUCER
AOUT1
AOUT2
AOUT3
AOUT4
COMP A1
COMP A2
COMP B1
COMP B2
SEE
NOTE
BELOW
NOTE:
DIGITAL COMPRESSORS = 1.5-5VDC
VFD COMPRESSORS = 0-10VDC
WattMaster Label
#S
000063
Rev.: 1B
W
E-BUS
HSSC
CONNECT
M
ENTER
UP
DOWN
ALARM
MENU
OE334-26-WSHP-X2 WSHP-X2 MODULE
AAON NO.: V48820
+24 V
A
C
GND
www.orioncontrols.com
www.aaon.com
- COMP A1 EN
- HEAT ENABLE
- COMP A2 EN
- H2O POF A
- COMP B1 EN
- H2O POF B
- COMP B2 EN
- COMMON
GND
- LEAVING WATER TEMP
- GROUND
- LEAVING WATER TEMP
AOUT1
- COMP A1
DIGITAL/VFD COMPRESSORS
A1, A2, B1, B2
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP. A2 ENABLE
COMP. A1 ENABLE
R1
R2
R3
R4
R5
RC
RELAY COMMON
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
CONNECT TO
CNTLR C2
TERM.
+5V
PRES
GND
+5V
PRES
GND
SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
NON-DIGITAL COMPRESSORS
AOUT2
- COMP A2
AOUT3
- COMP B1
AOUT4
- COMP B2
E-BUS
HSSC
CONNECT
BIN1
BIN2
BIN3
BIN4
BIN5
BIN6
BIN7
COM
T 1
T 2
LEAVING WATER
TEMPERATURE
FOR SYSTEM B
Connect To Other
WattMaster-Approved
E-BUS Expansion
Module(s)
Connect To
VCM-X E-BUS