Zone
Zone
VCM-X E-BUS Controller Wiring
VCM-X Component & Systems Wiring
34
Figure 14: OE217-00 / OE217-01 Digital Room Sensor
Digital Room Sensor & Wall-Mounted CO
2
Sensor Wiring
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
Digital Room Sensor
JOB NAME
01/09/13
O-VCM-X-DigiRoom-1A.CDR
VCM-X E-BUS Controller
1 of 1
I2C DIGITAL
SENSOR
I2C
EXPANSION
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
WattMaster Label
#LB102033-01
AI1
I1
SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
A
I7 SET
AI2
AI3
AI4
AI5
AI7
VCM-X E-BUS
Controller
OE217-00 / OE217-01
Digital Room Sensor
Display
Override
OVERRIDE
ALARM
TSDRSC Cable
Note: When Only The
Connects Directly To The VCM-X E-BUS
Controller Using A
Of The
Appropriate Length.
Digital Room Sensor
Is Used, It
TSDRSC Cable
The Maximum Length Allowed Is
160 Feet. See
For Connection When The
Space CO Sensor Is Also Used.
Figure 19
2
EMERGENCY SHUTDOWN
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
Wall-Mounted CO2 Sensor
JOB NAME
01/09/13
O-VCM-X-WallCO2-1A.CDR
VCM-X E-BUS Controller
1 of 1
I2C DIGITAL
SENSOR
I2C
EXPANSION
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
WattMaster Label
#LB102033-01
AI1
I1
SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
OE217-00 / OE217-01
Digital Room Sensor
OE256-01
CO Sensor
2
TSDRSC Cable
TSDRSC Cable
Display
Override
OVERRIDE
ALARM
Note: When a Digital Room Sensor Is
Used In Combination With The
The
r Always
Connects To The VCX E-BUS Controller
First Using a TSDRSC Cable Of The
Length. The Digital Room
Sensor Then Connects To The CO
Sensor With Another TSDRSC Cable.
CO
Sensor,
CO Senso
Required
Mount Sensor(s) At Least 5 Feet Above
Floor. See The
For Further Wiring Details.
2
2
2
C
Sensor Technical
Guide
O
2
EMERGENCY SHUTDOWN
VCM-X E-BUS
Controller
Note: In This Configuration,
Set The
Sensor To
Address 1.
CO
2
REVISED:
05/12/15
Figure 15: OE256-01 Wall-Mounted CO
2
Sensor