System commissioning overview, Vcm-x component & systems wiring 20, Stand alone system – Orion System VCM-X E-BUS Component User Manual
Page 20: Interconnected system, Networked systems

VCM-X Component & Systems Wiring
20
System Commissioning
Overview
The following information is a brief overview of the procedures
required to commission a typical Orion System. Select the type of
system that you have and follow the procedures listed for that system.
Stand Alone System
1. Be sure that the controller is set at address 1.
2. Apply power to the controller.
3. Verify diagnostics LED indicator for proper operation.
See the technical guide for the specifi c controller in
order to locate the diagnostic LED and controller start-
up
sequence.
4. Connect an operator’s interface device to the controller
for programming the controller.
Interconnected System
1. Be sure that the controllers are addressed from 1 to 60.
2. Apply power to the controllers.
3. Verify diagnostics LED indicator for proper operation
of all controllers. See the technical guide for the specifi c
controller in order to locate the diagnostic LED and
controller start-up sequence.
4. Connect an operator’s interface to one of the controllers
for programming all of the controllers.
Networked Systems
1. Address each MiniLink PD from 1 to 60.
2. On a loop of VCM-X E-BUS Controllers, address the
controllers from 1 to 59.
3. On a VAV or Zoning system, address VAV/Zone
Controllers from 1 to 58. Address the VCM-X E-BUS
Controller at 59.
4. On a VAV or Zoning system, apply power in the
following
order:
a.
VCM-X
E-BUS
Controller
b.
MiniLink
Polling
Device
c.
CommLink
5
d.
Power/Comm
boards
5.
Verify diagnostics LED indicator for proper operation of
all controllers. See the technical guide for the specifi c
controller in order to locate the diagnostic LED and
controller start-up sequence.
6. If a computer is used, connect it to the CommLink 5 to
access all of the controllers on the entire system for
programming.
7. If a computer is not used, and if a Modular System
Manager is not already connected on the local loop,
connect a Modular Service Tool or System Manager TS
II to one of the controllers to perform programming of
all controllers on the entire system.