Installation
|
25
Figure 5: Sample Humidification Applications
Room-Sensed %RH Feedback with Duct High-Limit Sensing (0-10V Signal Directly to Humidifier)
Configuration Variables
nviInputType_x
= 1
nviNetSensor_x
= 0
Control Variables
nviSet1_x
= Room Setpoint (0-100%)
nviSet2_x
= Hi-Limit Setpoint (0-100%)
nviRHDem1_x
= Room %RH (0-100%)
nviRHDem2_x
= Hi-Limit %RH (0-100%)
nviDisable_X
= 1 Unit Disabled
= 0 Unit Enabled
Readable Variables
nvoStatus_x
= 1 Humidifying
= 0 Standby
nvoService_x
= 1 Service Required
= 0 No Service Required
nvoFault_x
= 1 Fault
= 0 No Fault
nvoSysDemand_x = System Demand(0-100%)
nvoDisable_x
= 1 Unit Disabled
= 0 Unit Enabled