beautypg.com

Nortec LINKS 2 GSTC User Manual

Page 29

background image

Installation

|

25

Figure 5: Sample Humidification Applications

Room-Sensed %RH Feedback with Duct High-Limit Sensing (0-10V Signal Directly to Humidifier)


















Configuration Variables
nviInputType_x

= 1

nviNetSensor_x

= 0


Control Variables
nviSet1_x

= Room Setpoint (0-100%)

nviSet2_x

= Hi-Limit Setpoint (0-100%)

nviRHDem1_x

= Room %RH (0-100%)

nviRHDem2_x

= Hi-Limit %RH (0-100%)

nviDisable_X

= 1 Unit Disabled

= 0 Unit Enabled


Readable Variables
nvoStatus_x

= 1 Humidifying

= 0 Standby

nvoService_x

= 1 Service Required

= 0 No Service Required

nvoFault_x

= 1 Fault

= 0 No Fault

nvoSysDemand_x = System Demand(0-100%)
nvoDisable_x

= 1 Unit Disabled

= 0 Unit Enabled

This manual is related to the following products: