Nortec LINKS 2 GSTC User Manual
Page 18
14 | Installation
Table 4: Variable Definitions
Variable Name
R=Read
W=Write
Description
LonWorks SNVT
nvoRHDem1_x
R
Analog Value
Reads %RH in space or %demand
to humidifier. (0%-100%) Choice
determined by nviInputType_x.
SNVT_lev_percent
nvoSet1_x
R
Analog Value
Reads setpoint for relative humidity
in space. (0%-100%)
SNVT_lev_percent
nvoRHDem2_x
R
Analog Value
Reads duct %RH or secondary
space %RH, or secondary
%demand to humidifier. (0%-100%)
Choice determined by
nviInputType_x.
Dip Switch 4/5 on humidifier’s logic
board must be ON.
SNVT_lev_percent
nvoSet2_x
R
Analog Value
Reads setpoint for duct hi-limit
relative humidity, or setpoint for
secondary space relative humidity.
(0%-100%)
Dip Switch 4/5 on humidifier’s logic
board must be ON.
SNVT_lev_percent
nvoSysDemand_x
R
Analog Value
Reads humidifier system demand.
(0%-100%)
SNVT_lev_percent
nvoHourOpt_x
R
Analog Value
Indicates the number of hours the
humidifier has been in operation.
SNVT_time_hour
nvoServHours_x
R
Analog Value
Indicates the number of hours
remaining before the next service
interval.
SNVT_time_hour
nviRHDem1_x
W
Analog Value
Writes %RH in space or %demand
to humidifier. Choice determined by
nviInputType_x. (0%-100%)
SNVT_lev_percent
nviRHDem2_x
W
Analog Value
Writes duct %RH or secondary
space %RH, or secondary
%demand to humidifier. (0%-100%)
Choice determined by
nviInputType_x.
Dip Switch 4/5 on humidifier’s logic
board must be ON.
SNVT_lev_percent
nviSet1_x
W
Analog Value
Writes setpoint for relative humidity
in space. (0%-100%).
SNVT_lev_percent
nviSet2_x
W
Analog Value
Writes setpoint for duct hi-limit %RH,
or setpoint for secondary space
%RH. (0%-100%)
Dip Switch 4/5 on humidifier’s logic
must be ON.
SNVT_lev_percent
nvoRHDem1_x
R
Analog Value
Reads %RH in space or %demand
to humidifier. (0%-100%) Choice
determined by nviInputType_x.
SNVT_lev_percent