Nortec LINKS 2 GSTC User Manual
Page 26
22 | Installation
Table 11: Humidifier Variable Addresses - Unit #7
Unit #7
BACnet
Lonworks
N2
Variable Name
Type
Instance
SNVT
SNVT # NV Index Element Type Instance
nvoHourOpt_7
AV
85
SNVT_time_hour
124
139
1
AI
85
nvoRHDem1_7
AV
86
SNVT_lev_percent
81
140
1
AI
86
nvoSet1_7
AV
87
SNVT_lev_percent
81
141
1
AI
87
nvoRHDem2_7
AV
88
SNVT_lev_percent
81
142
1
AI
88
nvoSet2_7
AV
89
SNVT_lev_percent
81
143
1
AI
89
nvoSysDemand_7
AV
90
SNVT_lev_percent
81
144
1
AI
90
nvoServHours_7
AV
91
SNVT_time_hour
124
145
1
AI
91
nviRHDem1_7
AV
92
SNVT_lev_percent
81
146
1
AO
92
nviRHDem2_7
AV
93
SNVT_lev_percent
81
147
1
AO
93
nviSet1_7
AV
94
SNVT_lev_percent
81
148
1
AO
94
nviSet2_7
AV
95
SNVT_lev_percent
81
149
1
AO
95
Analog Expansion_7
AV
96
N/A
N/A
N/A
N/A
N/A
N/A
Analog Expansion_7
AV
97
N/A
N/A
N/A
N/A
N/A
N/A
nviDisable_7
AV
98
SNVT_switch
95
158
2
BO
98
nvoInputType_7
BV
85
SNVT_switch
95
150
2
BI
85
nvoFault_7
BV
86
SNVT_switch
95
151
2
BI
86
nvoNetSensor_7
BV
87
SNVT_switch
95
152
2
BI
87
nvoDisable_7
BV
88
SNVT_switch
95
153
2
BI
88
nvoService_7
BV
89
SNVT_switch
95
154
2
BI
89
nvoStatus_7
BV
90
SNVT_switch
95
155
2
BI
90
nvoKeepWarm_7
BV
91
SNVT_switch
95
156
2
BI
91
nvo3DayDrain_7
BV
92
SNVT_switch
95
157
2
BI
92
Expansion1_7
BV
93
N/A
N/A
N/A
N/A
N/A
N/A
nviInputType_7
BV
94
SNVT_switch
95
159
2
BO
94
nviNetSensor_7
BV
95
SNVT_switch
95
160
2
BO
95
nvoConnection
BV
96
SNVT_switch
95
161
2
BO
96
Expansion2_7
BV
97
N/A
N/A
N/A
N/A
N/A
N/A
Expansion3_7
BV
98
N/A
N/A
N/A
N/A
N/A
N/A