Nortec LINKS 2 GSTC User Manual
Page 21
Installation
|
17
Table 6: Humidifier Variable Addresses - Unit #2
Unit #2
BACnet
Lonworks
N2
Variable Name
Type
Instance
SNVT
SNVT # NV Index Element Type Instance
nvoHourOpt_2
AV
15
SNVT_time_hour
124
24
1
AI
15
nvoRHDem1_2
AV
16
SNVT_lev_percent
81
25
1
AI
16
nvoSet1_2
AV
17
SNVT_lev_percent
81
26
1
AI
17
nvoRHDem2_2
AV
18
SNVT_lev_percent
81
27
1
AI
18
nvoSet2_2
AV
19
SNVT_lev_percent
81
28
1
AI
19
nvoSysDemand_2
AV
20
SNVT_lev_percent
81
29
1
AI
20
nvoServHours_2
AV
21
SNVT_time_hour
124
30
1
AI
21
nviRHDem1_2
AV
22
SNVT_lev_percent
81
31
1
AO
22
nviRHDem2_2
AV
23
SNVT_lev_percent
81
32
1
AO
23
nviSet1_2
AV
24
SNVT_lev_percent
81
33
1
AO
24
nviSet2_2
AV
25
SNVT_lev_percent
81
34
1
AO
25
Analog Expansion_2
AV
26
N/A
N/A
N/A
N/A
N/A
N/A
Analog Expansion_2
AV
27
N/A
N/A
N/A
N/A
N/A
N/A
nviDisable_2
AV
28
SNVT_switch
95
43
1
AO
28
nvoInputType_2
BV
15
SNVT_switch
95
35
2
BI
15
nvoFault_2
BV
16
SNVT_switch
95
36
2
BI
16
nvoNetSensor_2
BV
17
SNVT_switch
95
37
2
BI
17
nvoDisable_2
BV
18
SNVT_switch
95
38
2
BI
18
nvoService_2
BV
19
SNVT_switch
95
39
2
BI
19
nvoStatus_2
BV
20
SNVT_switch
95
40
2
BI
20
nvoKeepWarm_2
BV
21
SNVT_switch
95
41
2
BI
21
nvo3DayDrain_2
BV
22
SNVT_switch
95
42
2
BI
22
Expansion1_2
BV
23
N/A
N/A
N/A
N/A
N/A
N/A
nviInputType_2
BV
24
SNVT_switch
95
44
2
BO
24
nviNetSensor_2
BV
25
SNVT_switch
95
45
2
BO
25
nvoConnection
BV
26
SNVT_switch
95
46
2
BO
26
Expansion2_2
BV
27
N/A
N/A
N/A
N/A
N/A
N/A
Expansion3_2
BV
28
N/A
N/A
N/A
N/A
N/A
N/A