Nortec LINKS 2 GSTC User Manual
Page 23
Installation
|
19
Table 8: Humidifier Variable Addresses - Unit #4
Unit #4
BACnet
Lonworks
N2
Variable Name
Type
Instance
SNVT
SNVT # NV Index Element Type Instance
nvoHourOpt_4
AV
43
SNVT_time_hour
124
70
1
AI
43
nvoRHDem1_4
AV
44
SNVT_lev_percent
81
71
1
AI
44
nvoSet1_4
AV
45
SNVT_lev_percent
81
72
1
AI
45
nvoRHDem2_4
AV
46
SNVT_lev_percent
81
73
1
AI
46
nvoSet2_4
AV
47
SNVT_lev_percent
81
74
1
AI
47
nvoSysDemand_4
AV
48
SNVT_lev_percent
81
75
1
AI
48
nvoServHours_4
AV
49
SNVT_time_hour
124
76
1
AI
49
nviRHDem1_4
AV
50
SNVT_lev_percent
81
77
1
AO
50
nviRHDem2_4
AV
51
SNVT_lev_percent
81
78
1
AO
51
nviSet1_4
AV
52
SNVT_lev_percent
81
79
1
AO
52
nviSet2_4
AV
53
SNVT_lev_percent
81
80
1
AO
53
Analog Expansion_4
AV
54
N/A
N/A
N/A
N/A
N/A
N/A
Analog Expansion_4
AV
55
N/A
N/A
N/A
N/A
N/A
N/A
nviDisable_4
AV
56
SNVT_switch
95
89
N/A
AO
56
nvoInputType_4
BV
43
SNVT_switch
95
81
2
BI
43
nvoFault_4
BV
44
SNVT_switch
95
82
2
BI
44
nvoNetSensor_4
BV
45
SNVT_switch
95
83
2
BI
45
nvoDisable_4
BV
46
SNVT_switch
95
84
2
BI
46
nvoService_4
BV
47
SNVT_switch
95
85
2
BI
47
nvoStatus_4
BV
48
SNVT_switch
95
86
2
BI
48
nvoKeepWarm_4
BV
49
SNVT_switch
95
87
2
BI
49
nvo3DayDrain__4
BV
50
SNVT_switch
95
88
2
BI
50
Expansion1_4
BV
51
N/A
N/A
N/A
N/A
N/A
N/A
nviInputType_4
BV
52
SNVT_switch
95
90
2
BO
52
nviNetSensor_4
BV
53
SNVT_switch
95
91
2
BO
53
nvoConnection
BV
54
SNVT_switch
95
92
2
BO
54
Expansion2_4
BV
55
N/A
N/A
N/A
N/A
N/A
N/A
Expansion3_4
BV
56
N/A
N/A
N/A
N/A
N/A
N/A