Configuring the humidifiers – Nortec LINKS 2 GSTC User Manual
Page 10
6 | Installation
Configuring The Humidifiers
Since Nortec Links2 can connect to a maximum of 8 units, it will be necessary to set the unit address
for each humidifier. The lead unit can be determined by the presence of the Links module. The slave
humidifiers can be given a unit address according to the number the unit will have on the networked
chain.
1. Press the Menu button on the keypad and enter the code 0335.
2. Select Control Settings
3. Select Modbus Paramaters.
4. Set the communication parity to None.
5. Set the appropriate Modbus address according to the unit ordering
6. Place the appropriate Unit Identifier label on each humidifier. These labels should be placed on
the unit where the electrical control punch-outs are located at the top of the humidifier.
7. Connect the slave humidifiers (if applicable) to the Nortec Links Module. A twisted pair cable
should be used so that the Net (+) terminal on the Links module should connect to the first pin
(bottom-most pin) of the connector. The Net (
–) terminal on the module should be connected to
the second pin of the connector. Refer to the unit’s wiring diagram for more information.
8. Ensure shield wiring matches the following pattern if distances between humidifiers is significant.