10 | Installation
Gateway Configuration
Protocol configuration is made at the factory, prior to final testing. Baud rates are adjusted to the 
following values by default. 
Table 3: Baud Rates
Protocol
Default Baud Rates
BACnet MS/TP
38.4 kbps
BACnet / IP
10BaseT
Johnson N2
9.6 kbps
LonWorks
38.4 kbps
For BACnet/IP, BACnet/MSTP and Johnson N2 applications, it is necessary to establish the 
modules network address parameters in order access it. Address assignments can be configured 
at the factory or Nortec can provide instructions to modify the address settings in the field. 
LonWorks networks can automatically detect network address parameters and do not need 
further configuration. 
Network Integration
LonWorks.xif file
To facilitate the integration of a LonWorks unit within a network, it may be desirable to obtain an 
External Interface File (XIF). Files of type .xif are used to convey the resources, specific objects 
and data types which a LonWorks device possesses. The .xif file allows a network integrator to 
simulate the presence of a networked humidifier even if it is not yet physically connected to the 
network. In fact, if the integrator has the .xif files of all network devices, a complete system could 
be simulated and configured off-line. Once the configuration is done, the integrator's software tool 
can be connected to the actual system and the configuration information can be downloaded. 