Table 5: Humidifier Variable Addresses – Unit #1

GSTC/SETC LINKS 2 Variable Listing
Default BACnet/IP Address: 192.168.10.11; Subnet: 255.255.255.0
Default BACnet/MSTP Address: 79
Default Johnson N2 Address: 175
Default unless otherwise requires at time of order.

Unit #1

BACnet

Lonworks

N2

Variable Name

Type

Instance

SNVT

SNVT # NV Index Element Type Instance

nvoHourOpt_1

AV

1

SNVT_time_hour

124

1

1

AI

1

nvoRHDem1_1

AV

2

SNVT_lev_percent

81

2

1

AI

2

nvoSet1_1

AV

3

SNVT_lev_percent

81

3

1

AI

3

nvoRHDem2_1

AV

4

SNVT_lev_percent

81

4

1

AI

4

nvoSet2_1

AV

5

SNVT_lev_percent

81

5

1

AI

5

nvoSysDemand_1

AV

6

SNVT_lev_percent

81

6

1

AI

6

nvoServHours_1

AV

7

SNVT_time_hour

124

7

1

AI

7

nviRHDem1_1

AV

8

SNVT_lev_percent

81

8

1

AO

8

nviRHDem2_1

AV

9

SNVT_lev_percent

81

9

1

AO

9

nviSet1_1

AV

10

SNVT_lev_percent

81

10

1

AO

10

nviSet2_1

AV

11

SNVT_lev_percent

81

11

1

AO

11

Analog Expansion

AV

12

N/A

N/A

N/A

N/A

N/A

N/A

Analog Expansion

AV

13

N/A

N/A

N/A

N/A

N/A

N/A

nviDisable_1

AV

14

SNVT_switch

95

20

2

AO

14

nvoInputType_1

BV

1

SNVT_switch

95

12

2

BI

1

nvoFault_1

BV

2

SNVT_switch

95

13

2

BI

2

nvoNetSensor_1

BV

3

SNVT_switch

95

14

2

BI

3

nvoDisable_1

BV

4

SNVT_switch

95

15

2

BI

4

nvoService_1

BV

5

SNVT_switch

95

16

2

BI

5

nvoStatus_1

BV

6

SNVT_switch

95

17

2

BI

6

nvoKeepWarm_1

BV

7

SNVT_switch

95

18

2

BI

7

nvo3DayDrain_1

BV

8

SNVT_switch

95

19

2

BI

8

Expansion1_1

BV

9

N/A

N/A

N/A

N/A

N/A

nviInputType

BV

10

SNVT_switch

95

21

2

BO

10

nviNetSensor

BV

11

SNVT_switch

95

22

2

BO

11

nvoConnection

BV

12

SNVT_switch

95

23

2

BO

12

Expansion2_1

BV

13

N/A

N/A

N/A

N/A

N/A

Expansion3_1

BV

14

N/A

N/A

N/A

N/A

N/A