Nortec LINKS 2 GSTC User Manual
Page 24
20 | Installation
Table 9: Humidifier Variable Addresses - Unit #5
Unit #5
BACnet
Lonworks
N2
Variable Name
Type
Instance
SNVT
SNVT # NV Index Element Type Instance
nvoHourOpt_5
AV
57
SNVT_time_hour
124
93
1
AI
57
nvoRHDem1_5
AV
58
SNVT_lev_percent
81
94
1
AI
58
nvoSet1_5
AV
59
SNVT_lev_percent
81
95
1
AI
59
nvoRHDem2_5
AV
60
SNVT_lev_percent
81
96
1
AI
60
nvoSet2_5
AV
61
SNVT_lev_percent
81
97
1
AI
61
nvoSysDemand_5
AV
62
SNVT_lev_percent
81
98
1
AI
62
nvoServHours_5
AV
63
SNVT_time_hour
124
99
1
AI
63
nviRHDem1_5
AV
64
SNVT_lev_percent
81
100
1
AO
64
nviRHDem2_5
AV
65
SNVT_lev_percent
81
101
1
AO
65
nviSet1_5
AV
66
SNVT_lev_percent
81
102
1
AO
66
nviSet2_5
AV
67
SNVT_lev_percent
81
103
1
AO
67
Analog Expansion_5
AV
68
N/A
N/A
N/A
N/A
N/A
N/A
Analog Expansion_5
AV
69
N/A
N/A
N/A
N/A
N/A
N/A
nviDisable_5
AV
70
SNVT_switch
95
112
1
AO
70
nvoInputType_5
BV
57
SNVT_switch
95
104
2
BI
57
nvoFault_5
BV
58
SNVT_switch
95
105
2
BI
58
nvoNetSensor_5
BV
59
SNVT_switch
95
106
2
BI
59
nvoDisable_5
BV
60
SNVT_switch
95
107
2
BI
60
nvoService_5
BV
61
SNVT_switch
95
108
2
BI
61
nvoStatus_5
BV
62
SNVT_switch
95
109
2
BI
62
nvoKeepWarm_5
BV
63
SNVT_switch
95
110
2
BI
63
nvo3DayDrain__5
BV
64
SNVT_switch
95
111
2
BI
64
Expansion1_5
BV
65
N/A
N/A
N/A
N/A
N/A
N/A
nviInputType_5
BV
66
SNVT_switch
95
113
2
BO
66
nviNetSensor_5
BV
67
SNVT_switch
95
114
2
BO
67
nvoConnection
BV
68
SNVT_switch
95
115
2
BO
68
Expansion2_5
BV
69
N/A
N/A
N/A
N/A
N/A
N/A
Expansion3_5
BV
70
N/A
N/A
N/A
N/A
N/A
N/A