Nortec LINKS 2 GSTC User Manual
Page 19
Installation
|
15
Table 4: Variable Definitions - CONTINUED
Variable Name
R=Read
W=Write
Description
LonWorks SNVT
nvoSet1_x
R
Analog Value
Reads setpoint for relative humidity
in space. (0%-100%).
SNVT_lev_percent
nvoRHDem2_x
R
Analog Value
Reads duct %RH or secondary
space %RH, or secondary
%demand to humidifier. (0%-100%)
Choice determined by
nviInputType_x.
Dip Switch 4/5 on humidifier’s logic
board must be ON
SNVT_lev_percent
nvoDisable_x
R
Binary Value
Reads remote disable status.
0=humidifier enabled, 1=humidifier
disabled by network
SNVT_switch
nvoService_x
R
Binary Value
Reads service requirement status.
0=no service required, 1=service
required
SNVT_switch
nvoStatus_x
R
Binary Value
Reads humidifier status. 0=standby,
1=humidifying
SNVT_switch
nvoConnection_x
R
Binary Value
Indicates that the Nortec Links
module is communicating with the
humidifier
SNVT_switch
nvoKeepWarm_x
R
Binary Value
Indicates that the KeepWarm feature
has been enabled
SNVT_switch
nvo3DayDrain_x
R
Binary Value
Indicates that the 3 day drain feature
has been enabled
SNVT_switch
nviDisable_x
W
Binary Value
Writes remote disable status.
0=humidifier enabled, 1=humidifier
disabled from network
SNVT_switch
nviInputType_x
W
Binary Value
Writes the input type status.
0=unit accepts a %demand signal
1=unit accepts on/off signal
SNVT_switch
nviNetSensor _x
W
Binary Value
Writes configuration status for
network-enabled sensing or control.
0=%RH or %demand input is not
from the network
1=%RH or %demand input is from
the network
SNVT_switch