beautypg.com

Nortec GS Series User Manual

Page 79

background image

GS Series Installation | 76


FCF:FILL
CHECK FAULT


The fill valve has
been active for an
extended time
without increasing
a float level


Unit will not
operate without
accurate float level
reading.
Investigate before
restarting unit.


(1)

Ensure water line is open and that

adequate water supply and pressure

is available.

(2)

Check wiring to float board and

fill valve. Check strainer on fill valve inlet.

(3)

Check that drain valve, auxiliary

drain valve or manual drain switch

are not activated.

(4)

Check fill valve using diagnostic

output test. Consult factory.

DCF: DRAIN
CHECK

Drain Pump activated
for extended period
without changing
float level

Unit needs to drain
for optimal
performance

(1)

Back pressure from drain lines can slow draining of

unit.

(2)

Drain Pump could be obstructed.

Clean Drain pump. Check that the drain

Pump is powered.

(3)

Ensure Float Level Sensor connected and that

levels change on fill.


FIF: FLOAT
INCONSIST.


On startup the unit
registers that the
float levels do not
increase logically
from 1 to 5


Unit cannot
operate
without accurate
float level reading


(1)

Float level sensor is malfunctioning

(2)

Inspect all hoses. Inspect all. connections.

Consult factory.



FLF: FLOAT
LEVEL


More than one float
level is registering
at the same time


Unit cannot
operate
without accurate
float level readings.


(1)

Float level sensor Is malfunctioning.

Inspect all connections.

(2)

Ensure that hoses are properly

connected and unobstructed.

(3)

Ensure correct hose from fill valve is

connected to chamber. Consult factory.


KWF: KEEP
WARM FAULT


Keep Warm activated
but tank temperature
has not increased
within time allotted


Unit cannot
operate in such
condition.


(1)

Check connection to tank temperature

Sensor. Check to ensure no more than

One burner is disabled.

(2)

Check tank to See if hot (caution).

Check electrical Signal to sensor.

(3)

Tank temperature Sensor may be

Defective. Consult factory.


OTF: OVER
TEMP FAULT


The exhaust or tank
Safety sensor has
exceeded the safety
limit


Unit cannot
operate
in such condition


(1)

Check unit float system. Unit may not be

operating with the correct water levels.

(2)

Ensure that exhaust line is open and free

of obstructions.

(3)

Consult factory.


HMF: MAINT.
FAULT


The humidifier
maintenance interval
and 72hour window
for cleaning
has expired.


Unit cannot
operate
Is such a condition


(1)

Unit requires servicing. Consult

maintenance guide in the Nortec manual.

(2)

Service reminder must be cleared after

maintenance. Refer to manual.