23 | GS Series Installation

NORTEC SERIES

EXTERNAL CONTROLS WIRING CONNECTIONS

LOW VOLTAGE TERMINAL STRIPS
May 27 2008

NORTEC SERIES

EXTERNAL CONTROLS WIRING CONNECTIONS

LOW VOLTAGE TERMINAL STRIP

WA R N I N G : F a i l u r e t o w i r e t h e c o n t r o l l e r
i n a c c o r d a n c e w i t h t h e w i r i n g d i a g r a m
s u p p l i e d w i t h t h e u n i t c o u l d p e r m a n e n t l y
d a m a g e t h e e l e c t r o n i c s . S u c h e r r o r s w i l l
v o i d t h e u n i t w a r r a n t y.

- www.humidity.com -

EXTERNAL

INTERNAL

3 4

6

5

7

EXTERNAL

INTERNAL

Security Loop

24Vac

Signal

Input

"2”

Signal

Input

"1”

1

2

On/Off Control
Humidistat

Air Proving
Switch

High Limit
Humidistat

Blower
Pack

Other On / Off
Device

NOTE: If no On/Off Control
is used then a field jumper
must be connected across
terminals 1 and 2 in order
for the humidifier to operate.

5

V

d

c

+ +

_

_

+

+

Single

Dual

POWER TO CONTROLLER OR

TRANSDUCER BY OTHERS

Both inputs to the

humidifier must be

the same type of

signal

Transducers:

Controllers (Humidistat):

Output signal across
3 - 4 and 3 - 5 increase
on RH rise

To be complete with RH
set point adjustment,
sensor circuit,
sensing element,
power source and
2 wire varying output signal.
RH demand are viewed on
display

Output signal across
3 - 4 and 3 - 5 decrease
on RH rise

To be complete with
sensing element,
power source and
2 wire varying output signal.
RH set point adjustment
is made at unit keypad.
RH set point and % RH
sensed are viewed on display

For all controller and transducer signals by others

8

2

4

V

a

c

Terminal 8 is a 24Vac input.
Upon receiving 24Vac a full tank
blowdown will be initiated

Figure 15: GS Series External Controls and Wiring Connections Low Voltage Terminal Strip