Rh settings, Cnt set-p – Nortec GS Series User Manual
Page 63
GS Series Installation | 60
Control Setting
LIM Type
: 0-10 V
Short CD
: On
Short CD T
: 300
Time Prop.
: On
Manual Cap.
: 100
ModBus Settings
Esc
Set
Time Proportioning
On
Off
On
Esc
Set
On
Time Prop.
: On
Time Proportioning
Allows the humidifier to modulate at low
demand.
Control Setting
Multi Mode
: StandAlone
CNT Type
: 0-10 V
Short CD
: Off
Time Prop.
: On
Manual Cap.
: 100
ModBus Settings
Esc
Set
Manual Capacity
100%
100%
Esc
Set
Manual Cap.
: 100
Manual Capacity
Allows the user to manually set the
maximum output of the humidifier.
RH Settings
The RH Settings submenu is used to adjust setpoint, the proportional band, and the integral time if REG
Mode is set to RH (P) or RH (PI) and the humidifier is connected to humidity sensors. Access the RH Settings
submenu by pressing the menu key while RH Settings is highlighted in the Control Settings menu.
CNT Set-P
Sets the humidity setpoint value. The
humidifier will attempt to maintain this
humidity level in the space where the
control transducer is installed.
Control Set Point
40% RH
40% RH
Menu
Set
CNT Set-P
: 40%
40% RH
RH Settings
CNT Set-P
: 40% RH
CNT Band
: 15% RH
CNT Itime
: 5 min
LIM Set-P
: 80% RH
LIM Band
: 15% RH
LIM Damp
: 5 s
RH Alerts
: On
RH High
: 75% RH
RH Low
: 33% RH
Menu
Set
CNT Set-P
: 40%
RH Settings
Only present if RH Alerts is set to On
Only present if MOD Mode is set to Dual CH