Nortec GS Series User Manual
Page 77

GS Series Installation | 74
 
FTW:FILL 
WARNING 
 
 
The fill valve has 
been active for an 
extended length of 
time and the water 
level is still zero 
 
Fill valve remains 
activated. Warning 
will change to fault 
if float level 
remains at zero. 
 
(1) Ensure water line is open and that 
 
adequate water supply and pressure
is available.
(2) Check wiring to float board and 
 
fill valve. Check strainer on fill valve inlet.
(3) Check that drain valve, auxiliary 
 
drain valve or manual drain switch
are not activated.
(4) Check fill valve using diagnostic 
 
output test. Consult Factory.
 
RHW:RH HIGH 
WARNING 
 
 
The measured RH is 
above the RH High 
alarm setting. 
 
The humidifier will 
remain idle until 
the measured RH 
drops below 
setpoint. 
 
(1) Check that RH high setting is correct 
 
for the application.
(2) Check sensor location (too close to steam 
 
distributor or other sources that affect
measurement).
(3) System may be oversized. 
 
Lower manual capacity of the unit.
(4) Consult Factory.
 
RLW:RH LOW 
WARNING 
 
The measured RH is 
below the “RH Low” 
alarm setting. 
 
 
The humidifier 
should be 
operating unless in 
standby or lockout 
mode. 
 
(1) Check that RH low setting is correct 
 
for the application.
(2) Check sensor location (too close to door, 
 
window, or other sources that affect
measurement).
(3) Humidifier may be in lockout or standby. 
 
Check security loop. Check that all burners
operational.
(4) System may be undersized. Check manual capacity 
 
setting. Consult factory.
 
RMW:RH LIMIT 
WARNING 
 
 
The RH input 
is lower than 3%. 
 
Operation is 
interrupted until an 
input higher than 
3% 
is received. 
 
(1) Check connection between sensor and 
 
unit.
(2) Check that sensor is functional.
(3) Ensure controls are located such that 
 
they provide accurate readings.
(4) Consult factory.
 
NSW:NO 
SIGNAL 
WARNING 
 
 
No communication 
is detected from 
Master unit. 
(This unit is set up 
as slave) 
 
Operation is 
interrupted until 
signal is received. 
 
(1) Verify that one unit is configured as 
 
master.
(2) Check connection between master and slave.
(3) Consult factory.
 
RDW: REMOTE 
DISABLED 
 
 
The unit has been 
remotely disabled 
through modbus 
communication or 
Nortec Online. 
 
Operation is 
interrupted until 
unit is re-enabled 
via modbus or 
software. 
 
(1) Enable unit through building management 
 
system (BMS) or Nortec Online.
(2) If unit cannot be enabled remotely, 
 
try enabling unit under software
Modbus Settings.
(3) Consult factory.
 
NBW: NO 
BURNERS 
AVAIL 
 
 
All burners have been 
disabled via software. 
No burners are 
available for operation. 
 
The unit will not be 
able to respond to 
a demand until 1 or 
more burners are 
enabled. 
 
 