Cnt band, Int time, Lim set-p – Nortec GS Series User Manual
Page 64: Lim band, Limit damping
61 | GS Series Installation
CNT Band
CNT Band should not normally be changed.
The CNT Band setting adjusts the band
within which the humidifier will modulate
between 0 and 100% output. (Default =
15%)
Int Time
Int Time should not normally be changed. Int
Time adjusts the frequency at which the
controller corrects for proportional control
error. It is only displayed if REG Mode is set
to RH (PI)
LIM Set-P
Sets the duct high limit setpoint value. As
RH in the duct approaches the high limit the
output of the humidifier will be throttled
back to prevent wetting the duct. (Default =
80%)
LIM Band
Should not normally be changed. The LIM
Band setting adjusts the band within which
the humidifier will throttle down the
humidifier output from 100 to 0%. (Default
= 15%)
Limit Damping
Sets the number of seconds the sensed RH
must exceed the limit band before output is
throttled down. (Default = 5 s)
Control Band
15% RH
15% RH
Menu
Set
CNT Band
: 15% RH
15% RH
Limit Set Point
80% RH
80% RH
Menu
Set
LIM Set-P
: 80%
80% RH
Limit Band
15% RH
15% RH
Menu
Set
LIM Band
: 15% RH
15% RH
Limit Damping
5 s
5 s
Menu
Set
LIM Damp
: 15% RH
5 s
Control Integral Time
5 min
5 min
Menu
Set
CNT Itime
: 5 min
5 min