Nortec GS Series User Manual
Page 62
59 | GS Series Installation
Control Setting
REG Mode
: Demand
MOD Mode
: Single CH
Multi Mode
:StandAlone
CNT Type
: 0-10V
LIM Type
: 0-10V
Short CD
: On
Set
Set
Multi Mode
StandAlone
StandAlone
Master
Slave
Set
Set
StandAlone
Multi Mode
: StandAlone
Multi Mode
Sets the humidifier to either
independent operation (StandAlone) or
linked operation (Master or Slave).
Note: If Master or Slave is selected
see Multi Unit Op. Range Settings,
displayed after the Manual Capacity.
Control Setting
MOD Mode
: Dual CH
Multi Mode
: StandAlone
CNT Type
: 0-10 V
LIM Type
: 0-10 V
Short CD
: On
Short CD T
: 300
Esc
Set
CNT Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
3.2-16 V
0-20 mA
4-20 mA
Esc
Set
0-10 V
CNT Type
: 0-10V
CNT Type
Configures the voltage or amperage
range of the control signal. Verify that
the signal matches the controller
(humidistat, transducer or network
connection).
Control Setting
Multi Mode
: StandAlone
CNT Type
: 0-10V
LIM Type
: 0-10 V
Short CD
: On
Short CD T
: 300
Time Prop.
: On
Esc
Set
LIM Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
3.2-16 V
0-20 mA
4-20 mA
Esc
Set
0-10 V
LIM Type
: 0-10V
LIM Type
Configures the voltage or amperage
range of the high limit control signal.
Verify that the signal matches the high
limit controller.
Control Setting
CNT Type
: 0-10V
Lim Type
: 0-10V
Short CD
: Off
Short CD T
: 300
Time Prop
: On
Manual Cap.
: 100
Esc
Set
Short Cycle Delay
Off
Off
On
Esc
Set
On
Short CD
: On
Short Cycle Delay
Prevents short cycling or frequent
turning on and off of humidifier. When
turned On, unit continues to operate for
set period of time after demand is met.
Note: When Short CD is turned On,
time must be specified. See Short CD T.
Control Setting
LIM Type
: 0-10V
Short CD
: Off
Short CD T
: 300
Time Prop
: On
Manual Cap.
: 100
ModBus Settings
Esc
Set
Short Cycle Delay Tm
300 s
300s
Esc
Set
Short CD T
: 300
Short Cycle Delay Time
Time humidifier stays on after demand
is satisfied.
Note: Short CD has to be turned On.
See above.