Table 10: GSTC Warning Troubleshooting
GSTC Warning 
Displayed 
 
 
Description of Warning 
 
Corrective action 
by unit 
Troubleshooting
IMW-X:IGNITION 
FAIL 
The Ignition module 
identified has failed to 
ignite within the allotted 
time 
(4 minutes). 
The unit will index 
to next available 
burner in the 
sequence. 
(1) Check sight port of problematic burner. Watch for 
 
hot igniter (glowing red) followed by a flame.
(2) If igniter not hot, check for voltage. 
 
Check wiring. Replace igniter if necessary.
(3) If igniter is hot but no flame, ensure gas supply 
 
connected. Check for 24V at gas valve.
(4) If flame visible, check flame sensor wiring. 
 
Check L1 not wired to N. Consult Factory.
 
APW-X:AP OPEN 
WARN 
 
 
The air proving 
switch identified has 
opened while the 
unit was operating. 
 
Unit will interrupt 
operation and retry 
three times. 
 
After a third try a 
fault is generated. 
 
(1) Ensure pressure tubes are secure. Check 
 
wiring to A/P switch and to driver board.
(2) Ensure blower is operating. if not, 
 
check wiring and power to blower.
Check blower relay.
(3) Perform blower diagnostic test to ensure A/P switch 
 
remains closed during operation.
(4) Check for suction In pressure tubes. If 
 
switch does not close it may be defective. Consult
Factory.
 
AOW-X:AP OPEN 
WARN 
 
 
The air proving switch 
identified did not close 
during blower start-up. 
 
Unit will interrupt 
operation and retry 
three times. 
 
After a third try a 
fault is generated. 
 
(1) Ensure pressure tubes are secure. 
 
Check wiring to A/P switch and to driver
board.
(2) Ensure blower is operating. If not, check wiring and 
 
power to blower. Check blower relay
.
(3) Perform blower diagnostic test to ensure A/P switch 
 
remains closed during operation.
(4) Check for suction In pressure tubes. If 
 
switch does not close it may be defective.
Consult Factory.
 
BHW-X:BLOWER 
RPM HIGH 
 
 
The indicated blower 
has an RPM higher 
than the lead blower 
by more than the 
allowable tolerance. 
 
The unit will keep 
monitoring blower 
RPM and display 
this warning if RPM 
remains high. 
 
(1) Ensure pressure tubes are secure. 
 
Check wiring to A/P switch and to driver
board.
(2) Ensure blower is operating. If not check wiring and
power to blower. Check blower relay.
(3) Perform blower diagnostic test to ensure A/P switch 
 
remains closed during operation.
(4) Check for suction In pressure tubes. If 
 
switch does not close it may be defective.
Consult Factory.
 
BLW-X:BLOWER 
RPM LOW 
 
The indicated blower 
has an RPM lower 
than the lead blower 
by more than the 
allowable tolerance. 
 
The unit will keep 
monitoring blower 
RPM and display 
this warning if RPM 
remains low. 
 
(1) Ensure blower in question is securely 
 
connected and is receiving correct
voltage.
(2) Verify blower control wiring connection. 
 
Check blower diagnostic test for abnormalities.
(3) Ensure no restriction on blower. 
 
Ensure no blockage of blower inlet.
(4) Blower speed may decrease due to wear. Safe to operate but 
 
output may be reduced. Order new blower.
 
HMW: MAINT. 
WARNING 
 
 
The preset service 
interval time has 
expired. 
 
The unit will 
continue to run for 
200 hours before a 
fault is generated. 
 
(1) Service unit. Consult maintenance 
 
guide in the Nortec manual.
(2) Reset service interval time after 
 
maintenance has been completed.