Idle only: humidifier is on standby – Nortec GS Series User Manual
Page 69
GS Series Installation | 66
User Defined Setting
BD rate
: 25
FTBD
: On
FTBD Time
: 23:30
FTBD Hours
: 100
Idle Mode
: Idle Drain
Idle Drain
: 72
Esc
Set
FTBD Time
Hour
: 23
Minute
: 30
Esc
Set
FTBD Time
: 23:30
Hour : 23
Full Tank Blow Down Time
Set the desired time of day to
completely drain the tank and refill.
Note: Since the FTBD interrupts
humidifier operation, it is
recommended to set time outside
peak operation time.
User Defined Setting
FTBD
: On
FTBD Time
: 23:30
FTBD Hours
: 100
Idle Mode
: Idle Drain
Idle Drain
: 72
Fill Corr
: 100
Esc
Set
FTBD Hours
100 h
100 h
Esc
Set
FTBD Hours
: 100
Full Tank Blow Down Interval
Set the desired weighted time
interval between FTBDs.
Idle Mode
Idle Drain
Idle Only
Idle Drain
Keep Warm
Esc
Set
Idle Drain
User Defined Setting
FTBD Time
: 23:30
FTBD Hours
: 100
Idle Mode
: Idle Drain
Idle Drain
: 72
Fill Corr
: 100
Drain Corr
: 100
Esc
Set
Idle Mode
: Idle Drain
Idle Mode
Configures humidifier operation
when there is no call for humidity.
Idle Only: Humidifier is on standby.
Idle Drain: Humidifier drains after
specified idling time (see Idle Drain).
Keep Warm: Water in tank is kept
between 140-160ºF (60 -70ºC)
User Defined Setting
Idle Mode
: Idle Drain
Idle Drain
: 72
Fill Corr.
: 100
Drain Corr.
: 100
Float Ck
: 23:30
Date
: 01/01/09
Esc
Set
Fill Correction
100 %
100 %
Esc
Set
Fill Corr
: 100
Fill Correction
Adjust the fill on and fill off times.
Values above 100% will increase
the fill on time and values below
100% decrease fill on time.
User Defined Setting
Idle Drain
: 72
Fill Corr.
: 100
Drain Corr.
: 100
Float Ck
: 23:30
Date
: 01/01/09
Time
: 12:00:00
Esc
Set
Drain Correction
100 %
100 %
Esc
Set
Drain Corr
: 100
Drain Correction
Used to compensate for variation in
drain pump flow rates. The drain
correction adjusts the actual drain
duration by drain time. Increasing
drain correction increases drain
duration and decreasing correction
decreases drain time.