Wall or Duct Mounted Modulating Humidistat: Provides a modulating signal to the unit that represents the
output (up to 100%) required from the humidifier. Signal type can be changed in the field.
All GS models may be configured for either single or dual channel modulation. Control signals can be 0-10
VDC or 0-20 mA (0-5 VDC, 1-5 VDC, 4-20 mA and 2-10 VDC are also available). The unit must be ordered
from the factory for the desired signal type and number of channels. When configured for 2-channel
modulation the humidifier will generate steam only if both channels indicate a demand. If both channels are
demanding steam the humidifier will satisfy the lower demand signal.
Table 4: Current and Breaker Requirements for GS Series Units
Voltage (V)
Rated Amps (A)
Suggested Breaker (A)
GSTC/GSP 100 Indoor
120
2.1
15
208-240
1.1
15
GSTC/GSP 200 Indoor
120
3.7
15
208-240
1.9
15
GSTC/GSP 300 Indoor
120
5.3
15
208-240
2.7
15
GSTC/GSP 400 Indoor
120
6.8
15
208-240
3.5
15
GSTC/GSP 500 Indoor
120
8.4
15
208-240
4.3
15
GSTC/GSP 600 Indoor
120
10
15
208-240
5.2
15
GSTC Outdoor 100
120
6.3
15
208-240
3.2
15
GSTC Outdoor 200
120
7.4
15
208-240
4
15
GSTC Outdoor 300
120
13.7
20
208-240
6.9
15
GSTC Outdoor 400
120
15.2
20
208-240
7.7
15
GSTC Outdoor 500
120
21
30
208-240
10.6
15
GSTC Outdoor 600
120
22.6
30
208-240
11.5
15