3 | GS Series Installation
Figure 1: GSTC-100
CAUTION: Installation
Installation and service must be performed by a qualified installer, service agency or the
gas supplier
The GS produces steam at atmospheric pressure. No devices which could block steam
output should be connected to the steam outlet.
Steam lines must be installed so that no restriction can produce backpressure in the
humidifier. Failure to follow installation instructions will result in improper operation and
could void warranty.
Regardless of selecting On/Off or modulating control method, Nortec humidifiers must
have a closed circuit across its On/Off security loop control terminal to operate. Nortec
highly recommends the use of a high limit humidistat and an air proving switch in series
for this function.
CAUTION: Plumbing
Plumbing to be performed by a licensed plumber.
All plumbing work should be done according to local plumbing code.
Unit damage caused by water quality outside of the specified ranges is not covered under
warranty.