MovinCool Office Pro W20 Service Manual User Manual
Page 9

Operation Section
9
• Specifications are subject to change without notice.
< NOTE >
*1 : If the entering water temperature is below 68 °F (20 °C) or above 86 °F (30 °C), adjustment of the unit's water
regulating valve setting is required.
*2 : Measured at 3 feet (1.0 m) from surface of the unit.
Weight
Net
178 lb (81 kg)
Shipping
209 lb (95 kg)
Drain Tank Capacity
5.0 gal (19 L)
Operating Condition Range Inlet Air
Temperature
Max.
95 °F (35 °C), 60 %RH
Min.
65 °F (18 °C), 50 %RH
Entering Water
Temperature
*1
Max.
90 °F (32 °C)
Min.
40 °F (4.4 °C)
Water Pressure
150 psi (1034 kPa)
Recommended Water Flow Rate
4.8 gal/min (18 L/min)
Maximum Duct Length
Cold Duct
25 ft (7.6 m)
Sound Level
*2
High
62 dB (A)
Low
60 dB (A)
Safety Devices
Compressor Overload Protector
Included
Fan Motor Overload Protector
Included
Freeze Protection Thermistor
Included
Full Drain Tank Switch
Included
Automatic Restart (Power Interruption)
Included
Compressor Time Delay
120 sec
High Pressure Interruption
Included
Signal Input/Output
Included
Control Devices
Temperature Control
Included
Programmable Timer
Included
Two Speed Fan
Included
ITEM
SPECIFICATIONS