Caution – MovinCool Office Pro W20 Service Manual User Manual
Page 26

Operation Section
26
7) Write the value setting with a permanent marker
on the adjustment record table on the inside
panel of the unit.
< NOTE >
Recording the value setting is very important
for reference when making future adjustments.
Valve Setting Guide Table
Adjustment Record (Example)
CAUTION
Do not forget to write down the value setting with a permanent marker on the adjustment record
table. This is the only way to know the current valve setting. It is difficult to exactly adjust the
valve without the current valve setting. Failure to adjust the valve may damage the unit and void
the warranty.
Setting
Direction of Valve Rotation Number of Rotation Valve Opening Temperature
Minimum Water Temperature
A
Clockwise
4
72 °F (22 °C)
40 °F (4.4 °C)
B
3
75 °F (24 °C)
47 °F (8 °C)
C
2
79 °F (26 °C)
54 °F (12 °C)
D
1
82 °F (28 °C)
61 °F (16 °C)
E
Default Setting Point
-
86 °F (30 °C)
68 °F (20 °C)
F
Counterclockwise
1
90 °F (32 °C)
72 °F (22 °C)
G
2
94 °F (34 °C)
75 °F (24 °C)
H
3
96 °F (36 °C)
79 °F (26 °C)
I
4
100 °F (38 °C)
83 °F (28 °C)
No.
Setting Date
Setting
No.
Setting Date
Setting
0
-
E
11
•
Dec. 10, 2010
B
•
•
Apr. 10, 2011
D
•
•
Aug. 10, 2011
G
•
10
21