MovinCool Office Pro W20 Service Manual User Manual
Page 66
Repair Section
66
11.2 Removal of Refrigeration and Water System Components
WARNING
• Before replacing any refrigeration and water system component, recover the refrigerant
using standard recovery procedures and drain the water from the unit.
• When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)
and high pressure side (tube 2) as shown in the figure below.
CAUTION
• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min)) through
the pinch-off tube during any brazing operation.
• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,
to protect them from the flame.
< NOTE >
When replacing the compressor, attach the pipe 1 and the pipe 2 packaged in the compressor
assembly.
ILL00157-00
High Pressure Switch
D
I, L, M
Water Regulating Valve
Compressor
A, H
B, C, J, K
E, F, G
E, H
Condenser
Capillary Tube
Evaporator
Part to Replace
Disconnect At
D
F
G
H
I
J
K
Tube 2
Tube 1
L
M
C
E
A
Pipe 2
Pipe 1
B