MovinCool Office Pro W20 Service Manual User Manual
Page 34
Operation Section
34
7.2 Fire Alarm Control Panel Connection (Input Signal Terminal E+ and E-)
• The controller is equipped with a normal open input signal, which can be connected directly from
the fire alarm control panel. When receiving the signal from the fire alarm control panel, the unit
turns off and does not turn back until it has been reset.
Connecting fire alarm control panel to controller
1 ) Remove service panel from the rear of the unit.
3 ) Insert the fire alarm signal wire through the hole in the rear panel.
2 ) Squeeze the inner latches and push out the black cap from inside the panel. (See drawing of
Cap and inner latch shapes.)
Use recommended warning signal wire size from 16 AWG to 26 AWG for a solid wire, or 16
AWG to 22 AWG for a stranded wire with ring terminal for #6 stud size.
4 ) Connect warning device to terminal E+ and E- according to its polarities.
ILL00078-00
Latch
Unit Terminal
Output Signal
Fire Alarm Device
E+
E-
L+
L-
Open Dry Contact
ILL00080-00