13 (3) current consumption curve – MovinCool Office Pro W20 Service Manual User Manual
Page 13

Operation Section
13
(3) Current consumption curve
How to read the current consumption curve
< NOTE >
Water flow rate at 4.8 GPM is a reference value corresponding to various current consumption at
various entering water temperature. From reference curve, read current consumption at various
water flow rate (see example of how to read current consumption).
ILL00226-00
Current Consumption at 4.8 GPM (A)
Current Consumption (A)
35
(2)
45
(7)
55
(13)
65
(18)
75
(24)
85
(29)
95
(35)
2.4 3.6 4.8 6.0 7.2
8
14
9
10
11
12
13
8
9
10
11
12
13
14
Entering Water Temp. °F (°C)
Water Flow (GPM)
ILL00227-00
8
9
10
11
12
13
14
Current Consumption at 4.8 GPM (A)
Current Consumption (A)
35
(2)
45
(7)
55
(13)
65
(18)
75
(24)
85
(29)
95
(35)
2.4 3.6 4.8 6.0 7.2
8
14
9
10
11
12
13
Entering Water Temp. °F (°C)
Water Flow (GPM)
Example: EWT: 85 °F (29 °C), Water flow: 7.2 GPM
Current Consumption: 1.12 A
Reference
Value