Repair Section

71

(3) Checking vacuum

1) Leave the high pressure valve and the low

pressure valve of the gauge manifold closed for 5

minutes or more, and confirm that the gauge

pointer does not return to zero.

2) If the gauge pointer returns gradually to zero

there is a leak somewhere in the system (this

could also include gauge manifold). Perform leak

check according to procedure indicated in the

next step. Once leak has been found and

repaired, evacuate the system once more and

confirm the system holds vacuum.

ILL00085-00

Return

Pipe Brazing

LO

Closed

HI

Closed

Valve Setting

Pressure Gauge