Reassembly, 1 reassembly of unit, 2 compressor mounting – MovinCool Office Pro W20 Service Manual User Manual
Page 76: 3 evaporator fan assembly, 4 wiring notice, Reassembly of unit, Compressor mounting, Evaporator fan assembly, Wiring notice

Repair Section
76
12. REASSEMBLY
12.1 Reassembly of Unit
• Reassemble the unit in the reverse order of removal. Described below are the parts that require
special care in reassembling the unit. Perform all wiring or rewiring as referenced in the wiring
diagram.
12.2 Compressor Mounting
• Mount the compressor on the frame, using
cushions, steel collars, plate washers and nuts.
12.3 Evaporator Fan Assembly
• Install the evaporator fan. Allow a clearance of
0.06 inch (1.5 mm) or more between the
evaporator fan and the fan casing.
CAUTION
• Tightening torque:
- 10.84 ± 2.17 ft•lbf (7.4 ± 0.7 N•m)
12.4 Wiring Notice
• Secure the wires using clamps so that they do not come into contact with the edges of the
structure, etc. Secure the wires using clamps in the same position they were before removal.
ILL00178-00
Nut
Steel Collar
Cushion
Plate Washer
ILL00158-00
0.06 in
(1.5 mm)
or more