beautypg.com

Legrand RW3U600 User Manual

Page 3

background image

CAUTION

For your safety: Connecting a proper ground to the sensor provides protection

against electrical shock in the event of certain fault conditions. If a proper ground

is not available, consult with a qualified electrician before continuing installation.

3. Prepare the Wires.

Tag the wires currently connected to the existing switch

so that they can be identified later. Disconnect the wires.

Make sure the insulation is stripped off of the wires to

expose their copper cores to the length indicated by the

“Strip Gage,” in Fig. 3. (approx. 1/2 inch).

4. Wire the sensor.

Twist the existing wires together with the wire leads on the RW3U600 sensors as

indicated below. Cap them securely using wire nuts provided. (See Fig. 4 & 5)

• Connect the green or non-insulated (copper) GROUND wire from the circuit to

the green terminal on the RW3U600s.

• Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the

white wire on the master RW3U600.

The term “master” designates the RW3U600 that connects to the load.
• Connect the neutral wire from the circuit to the white wire on the auxiliary RW3U600.
• Connect the power wire from the circuit box (HOT) to the black wire on the

auxiliary RW3U600 and to the TRAVELER 1 wire.

• Connect the TRAVELER 1 wire from the black wire of the auxiliary RW3U600 to

the black wire of the master RW3U600.

• Connect the lamp power (LOAD) to the red wire on the master RW3U600.
• Cap the red wire on the auxiliary RW3U600.
• Connect the TRAVELER 2 wire coming from the yellow wire of another RW3U600

to the yellow wire of the RW3U600 that you are wiring.

5. Put the RW3U600s into their respective wall boxes.

Position them with the lens positioned

above the ON/OFF button (lens at top,

ON/OFF button at bottom). Secure to

the wall box with the screws provided.

6. Make any necessary

adjustments.

See the SENSOR ADJUSTMENT &

PROGRAMMING section for information.

7. Attach the new cover plate.

Secure it with the screws provided.

8. Restore power to the circuit.

Turn on the breaker or replace the fuse.

Fig. 4: Sensor orientation, wire connections and wall box assembly

Fig. 5: Reference wiring diagram

Initial Power-up

There is an initial warm-up

period. If the sensor is in Mode 2

“Automatic ON” it may take up to a

minute before the lights turn ON.

However, the lights can be turned

ON/OFF manually by pressing the

“ON/OFF Button” at anytime when

power is supplied to the unit.

Call 800.223.4185 for Technical Support

Fig. 3: Wire

Stripping

This manual is related to the following products: